Table 2-2. V/f Startup Procedure - Continued
Set Parameter n012-
Voltage Max.
(460.0 V)
Press then .
DATA
ENTER
V
Set Parameter n014-
Frequency - Midpoint
(30.0 Hz)
Press then .
DATA
ENTER
V
Set Parameter n013-
Frequency at max. voltage
point (motor rated frequency)
(60.0 Hz)
Press then .
DATA
ENTER
V
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
(1)
Then press
.
DATA
ENTER
Use the
&
keys until the
desired number is in the display.
V
V
Then press
.
DATA
ENTER
Use the
&
keys until the
desired number is in the display.
V
V
Then press
.
DATA
ENTER
Use the
&
keys until the
desired number is in the display.
V
V
(1)
(1)
(1)
(1)
(1)