background image

4 Drive Change Summary

10

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

Table 6 Additional or Modified Fault Codes for PRG: 0035

Table 7 Additional Alarms or Messages for PRG:0035

Table 8 Additional Alarms or Messages for PRG:0036

Fault Code

Description

Page

OPE13

Terminal A1

Displayed when terminal A1 is assigned to more than one function. OPE13 is modified from

the previous software version PRG:0034.

28

OPE17
Run/Stp-CoastTmr

Displayed when Run/Stop Control and Coast To Stop w/Timer are both enabled.

42

OPE18
Net Incompatible

Displayed when using features specific to iQpump software version 30035+ and nameplate
PRG: 0035 or greater with parameter P9-99 set to (0: A:Version 30034).

43

OPE19

Geothermal Set

Displayed when a parameter selection is not compatible with the Geothermal Mode

(b1-01 = 5) setting.

42

Temp Lost

Geothermal Input

Displayed when geothermal input is not present.

23

LOSUC
Low Suction

Suction pressure is below programmed level.

18

Alarm

Description

Page

Net FlowMeter

Lost, Chk Source

Displayed when there is no drive on the Memobus Network with an analog Flow Meter.

28

LOSUC
Low Suction

Displayed when Low City Pressure is active and alarm selection P4-27 = 1.

13

Low Water

in Tank

Displayed when Low City Pressure is active and alarm selection P4-27 = 2.

13

Temp Lost

Geothermal Input

Displayed when a geothermal input is not present.

23

R-DNE-S† <1>
Remote Drv Dis

<1> The † character is a place holder for the actual digital input designation, such as S1, S2, or S3.

Remote drive disable is active.

12

AnalogA1 Lost

Switched to Net

Displayed when there is a defective or broken analog input source. Analog Terminal A1 has

not been detected, and the Network Water Level or Suction Pressure signal is now used.

23

Net Wtr/Suctn

Lost, Chk Source

Displayed when a valid analog source for Water Level or Suction Control Pressure can not be

found on the network.

23

Alarm

Description

Page

OPE20

Net WL/SP Mode

Incompatible Network Water Level / Suction Pressure Mode.

-

Low WL/SP
Drive Disabled

Drive is unable to run because the Water Level or Suction Pressure is below the P8-05 setting.

-