YASKAWA TM.iQp.10 Technical Manual Supplement

57

E1-04

0303

Maximum Output
Frequency
Max Frequency

To set V/f characteristics in a straight line, set the same values for E1-07
and E1-09. In this case, the setting for E1-08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX) ˜ E1-06 (FA) > E1-07 (FB) ˜ E1-09 (FMIN)

0.0 ~

120.0 Hz

60.0 Hz

Programming

E1-05

0304

Maximum Output Voltage
Max Voltage

0.0 ~ 255.0

(240V)

0.0 to 510.0

(480V)

230.0 V

460.0 V

Programming

E1-06

0305

Base Frequency
Base Frequency

0.0 ~

200.0 Hz

60.0 Hz

Programming

E1-07

0306

Mid Output Frequency A
Mid Frequency A

0.0 ~

200.0 Hz

3.0 Hz

Programming

E1-08

0307

Mid Output Voltage A
Mid Voltage A

0.0 ~ 255.0

(240V)

0.0 to 510.0

(480V)

17.2 Vac
34.5 Vac

Programming

E1-09

0308

Minimum Output
Frequency
Min Frequency

0.0 ~

200.0 Hz

1.5 Hz

Programming

E1-10

0309

Mid Output Voltage
Min Voltage

0.0 ~ 255.0

(240V)

0.0 to 510.0

(480V)

10.3 Vac
20.7 Vac

Programming

E1-11

030A

Mid Output Frequency B
Mid Frequency B

Set only when V/f is finely adjusted at rated output range.
Adjustment is not normally required.

0.0 ~

200.0 Hz

0.0 Hz

Programming

E1-12

030B

Mid Output Voltage B
Mid Voltage B

0.0 ~ 255.0

(240V)

0.0 to 510.0

(480V)

0.0 Vac

Programming

E1-13

030C

Base Voltage
Base Voltage

0.0 ~ 255.0

(240V)

0.0 to 510.0

(480V)

0.0 Vac

Programming

Motor Setup

E2-01

030E

Motor Rated Current
Motor Rated FLA

Set to the motor nameplate full load amps.

10 ~

200 %

kVA

Dependent

Pump Quick

Setup

E2-03

030F

No-Load Current

Sets the magnetizing current of the motor.

kVA

Dependent

kVA

Dependent

Programming

E2-04

0311

Number of Motor Poles
Number of Poles

Set to the number of poles. Used for no-flow detection function and for the
calculation of rpm related parameters.

2 ~ 48

2

Pump Quick

Setup

E2-05

0312

Motor Line-to-Line
Resistance
Term Resistance

Phase to phase motor resistance, normally set by the autotuning routine.

0.000 ~

65.000

kVA

Dependent

Programming

Communication Option Setup

F6-01

03A2

Operation Selection after
Communication Error
Com Bus Flt Sel

Sets the stopping method for option PCB communications error (BUS
fault). Active only when a communications option PCB is installed and
when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

1

Programming

F6-02

03A3

Input Level of External
Fault from
Communication Option
Card
EF0 Detection

0: Always detected
1: Detected only during run

0 ~ 1

0

Programming

F6-03

03A4

Stopping Method for
External Fault from
Communication Option
Card
EF0 Fault Action

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

1

Programming

F6-05

03A6

Current Monitor Display
Unit Selection
Current Unit Sel

0: A Display
1: 100 % /8192 (Drive Rated Current)

0 ~ 1

0

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Output voltage (V)

Frequency (Hz)

FMIN FA FBASE FMAX

(E1-09) (E1-07) (E1-06) (E1-04)

VMAX
(E1-05)
VBASE
(E1-13)

VA
(E1-08)

VMIN
(E1-10)