6 Feature Details - Low City Pressure Alarm

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

13

6

Feature Details - Low City Pressure Alarm

‹

Overview

The alarm function is used for stopping the iQpump Controller or preventing the iQpump Controller from running based
on an external contact closure.

This function has been enhanced by parameter P4-27 which allows users to select the alarm message that will be
displayed when a Low City Pressure condition is detected.

„

Function Operation

P4-27 Low City Pressure Alarm Text

Selects the alarm message that will be displayed when a Low City Pressure condition is detected.

Alarm: Low Pressure/Low Water in Tank

„

Related Parameters

P4-21 Low City Pressure Input Select

P4-22 Low City Pressure Input Delay Time

Multi-function Input Setting H1-††: Low City Pressure

Setting

Description

0

Low City Pressure (factory default)

1

Low Suction Pressure

2

Low Water in Tank

Alarm Display

Description

Low Suction Pressure

Shown when P4-27 = 1 and when the digital input has been active (closed for P4-21 = 0, or open for

P4-21 = 1) for the time set in P4-22. The drive, if running, coasts-to-stop and does not run until the digital
input has been inactive for the time set in P4-22.

Low Water In Tank

Shown when P4-27 = 2 and when the digital input has been active

(closed for P4-21 = 0, or open for P4-21 = 1) for the time set in P4-22. The drive, if running, coasts-to-stop
and does not run until the digital input has been inactive for the time set in P4-22.

Setting

Description

0

Normally Open (closed for the "Low City Pressure" condition)

1

Normally Closed (open for the "Low City Pressure" condition) (factory default)

Range

Description

Default

1 - 1000 sec

Sets the amount of time a "Low City Pressure" condition must be present before
the drives will stop. Also sets the amount of time that the pressure must be

adequate before the drive system will restart.

10 sec

Setting

Description

73 Low City Pressure

Indicates that sufficient/insufficient pressure is present on the inlet to the pump. This setting is used mainly
for pressure booster stations.