YASKAWA TM.iQp.10 Technical Manual Supplement

Parameter List

Table 1 Parameter List

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Initialization

A1-00



0100

Language Selection
Select Language

Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
*Not returned to factory setting by initialization

0 ~ 6

0

Programming

A1-01



0101

Access Level Selection
Access Level

This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level

0 or 2

2

Programming

A1-03

0103

Initialize Parameters
Init Parameters

Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default values
and then parameter o2-03 must be set to “1” to save them. If the parameter
values are changed after o2-03 is set to “1”, the user default values can be
restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
7770: General Purpose <0035>

0 ~ 7770

0

Programming

A1-04

0104

Password 1
Enter Password

When the value set into A1-04 does NOT match the value set into A1-05,
parameters A1-01 thru A1-03 cannot be changed.
All other parameters as determined by A1-01 can be changed. Parameter
A1-05 can be accessed by pressing the MENU key while holding the
RESET key.

0 ~ 9999

0

Programming

A1-05

0105

Password 2
Select Password

0 ~ 9999

0

Programming

 Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.

Sequence

b1-01

0180

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see parameter
H3-13)
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Geothermal Mode - frequency reference dependent on temperature input
(H3-09=20) <0035>

0 ~ 5

0

Programming

b1-02

0181

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run

<0034>

0 ~ 3, 5

0

Programming

b1-03

0182

Stopping Method
Selection
Stopping Method

Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before the time
in C1-02 expires.)

0 ~ 3

1

Default =0
prior to
PRG:
<0035>

Programming

b1-04

<0035>

0183

Reverse Operation
Selection
Reverse Operation

1: Reverse Disabled
3: Exchange Phase, Reverse Disabled

1, 3

1

Programming

b1-07

0186

Local/Remote Run
Selection
LOC/REM RUN Sel

0: Cycle External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the drive will not run.
1: Accept External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the drive WILL run.
Note: Used with LCD Operator only.

0 ~ 1

0

Programming

b1-08

0187

Run Command Selection
During Program
RUN CMD at PRG

0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when
b1-02 = 0).

0 ~ 1

0

Programming

b1-11

010F

Drive Delay Time Setting
Wait to Run Time

After a run command, drive output will start after this delay time.

0 ~ 600 sec

0 sec

Programming