11 Improved and Miscellaneous Functions

38

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

‹

Initialization for Basic Applications (A1-03)

A new initialization mode setting 7770 is available under parameter A1-03 (Initialize Parameters). This setting allows
users to easily configure the iQpump Controller for use as a standard drive in simple applications. In this mode the
iQpump Controller defaults to start/stop operation from the terminals and speed control using a 0-10 Vdc signal to analog
input A1.

„

A1-03 Initialize Parameters

The Table below shows the default parameters settings for the standard iQpump Controller 2-wire initialization (2220)
and the General Purpose Initialization (7770).

„

Parameters Modified for General Purpose Initialization

Note: After performing a General Purpose initialization (7770), the parameters shown in this table will be visible in the Modified

Constants menu, with the exception of parameters marked by *.

Setting

Description

0

No Initialize (factory default)

1111

User Initialize
The modified iQpump Controller parameters are returned to the values selected as user settings. User

settings are stored when parameter o2-03 = 1: Set Defaults.

2220

2-Wire Initialize
Initializes the iQpump Controller for 2 Wire Control Operation

3330

3-Wire Initialize

Initializes the iQpump Controller for 3 Wire Control Operation

7770

General Purpose

Configures the iQpump Controller for General Purpose Operation

Parameter No.

Parameter Name

Factory Default Setting

Setting After General

Purpose Initialize

(A1-03 = 7770)

b1-01

Frequency Reference Selection 0 (Operator)

1 (Terminals)

b1-02

Run Command Selection

0 (Operator)

1 (Terminals)

b5-01

PID Mode Setting

1 (Enabled)

0 (Disabled)

C1-01

Acceleration Time 1

20.0 sec

25.0 sec

C1-02

Deceleration Time 1

10.0 sec

25.0 sec

C6-02

Carrier Frequency Selection

1 (2.0 kHz)

kVA dependent

H1-04

Terminal S6 Selection

80 (Hand Mode)

4 (Multi-Step SP 2)

H1-05

Terminal S7 Selection

84 (Disable Pre-Charge)

F (Term Not Used)

H2-01

Terminal M1-M2 Selection

40 (Pump 2 Control)

0 (During Run 1)

H2-02

Terminal M3-M4 Selection

41 (Pump 3 Control)

A (Remote/Auto Oper)

H3-09*

Terminal A2 Function Selection B (PID Feedback)

2 (Aux Reference)

L5-01

Number of Auto Restarts

5

0

L5-03

Maximum Restart Time

20.0 sec

180.0 sec

o1-06*

User Monitor Selection Mode

1 (3 Mon Selectable)

0 (3 Mon Sequential)

P1-02

System Units

1 (psi:lb/SqrInch)

14 (Hz: Hertz)

P1-03

Feedback Scaling

145

26000

P1-05

Start Level Delay Time

1 sec

0 sec

P1-06

Minimum Pump Frequency

40.0 Hz

0.0 Hz

P4-05

Thrust Frequency

30.00 Hz

0.00 Hz

P4-11

Utility Delay Time

0.2 minutes

0.0 minutes

P5-02

Hand Reference

40.00 Hz

0.00 Hz