12 Speed Follower Deceleration Time Switchover <0036>

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

45

P9-07 Lag Fixed Speed Delay

Time delay before execution of P9-05 selection when the iQpump Controller changes from lead to lag.

P9-30 Lag Drive Speed Follower Gain

P9-31 Lag Drive Speed Follower Bias

P9-99 Network Compatibility Selection

Determines the communication compatibility for the iQpump Memobus Network.

1

PI Regulation.
Uses PI to determine speed.

2

Turn Off

The iQpump Controller stops running when it switches to a lag drive after P9-07 time expires.

3

Follow Lead Spd

The iQpump Controller follows the speed of the active Lead drive. Use P9-30 gain and P9-31 bias setting

to adjust reference signal.

Range

Description

Default

0 - 1000 sec

When the drive changes from a lead to a lag and P9-05

≠ 1, this time specified

in parameter P9-07 determines how long the speed is latched before executing
one of the following operations:

1. P9-05 = 0: Run at P9-06
2. P9-05 = 2: Turn off
3. P9-05 = 3: Follow the Lead Drive's speed.

5 sec

Range

Description

Default

0.0 - 300.0 %

When P9-05 = 3, the drive will follow the speed of the active lead drive
applying this gain and P9-31 bias to the reference signal.

100.0 %

Range

Description

Default

-60.00 - 60.00 Hz

When P9-05 = 3, the drive will follow the speed of the active lead drive

applying this bias and P9-30 gain to the reference signal.

0.00 Hz

Setting

Description

0

A-Version 30034

Use this mode if (ONE or MORE) iQpump Controllers on the network have software version monitor U1-
14=30034 and nameplate PRG: 0034.

1

B-Version 30035+ (factory default)

Use this mode if (NONE) of the iQpump Controllers on the network have software version monitor U1-
14=30034 and nameplate PRG: 0034.

Setting

Description