Yaskawa iQpump Manual Supplement User Manual
Page 35
10 iQpump MEMOBUS/Network Operation
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
35
Related Parameters: Triplex Irrigation Booster System
Parameter
Description
PM Pump
Booster Pump 1 Booster Pump 2
H5-01
Drive Node Network Address
1
2
3
P1-01
Pump Mode
3
3
3
P1-03
FD Device Scaling
200 psi
200 psi
200 psi
P1-04
Start Level
-10.0 psi
-10.0 psi
-10.0 psi
P9-01
Lead Drive Select
2
2
2
P9-02
Feedback Source
2
2
2
P9-07
Lag Fixed Spd Dly
(PM Pump will shut off after 20 sec)
20 sec
5 sec
5 sec
P9-20
Allow Net Run
(PM Pump will be lead Pump to start)
2
0
0
P9-21
Run Priority
7
8
8
P9-24
Lead Swap @ Sleep
0 sec
1 sec
1 sec
P9-25
Highest Node Address
3
3
3
U1-01
Auto Setpoint
100 psi
100 psi
100 psi
Booster
Pump 1
Booster
Pump 2
Network
PM
Pump
3
p
m
u
p
Q
i
2
p
m
u
p
Q
i
iQpump 1
System
Pressure
Feedback
PM
V+
A2
AC
Tr
ansduc
er
10 HP
50 HP
50 HP
System
Pressure
Feedback
Pump 1
V+
A2
AC
Tr
ansd
uce
r
System
Pressure
Feedback
Pump 2
V+
A2
AC
Transducer