10 iQpump MEMOBUS/Network Operation

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

35

Related Parameters: Triplex Irrigation Booster System

Parameter

Description

PM Pump

Booster Pump 1 Booster Pump 2

H5-01

Drive Node Network Address

1

2

3

P1-01

Pump Mode

3

3

3

P1-03

FD Device Scaling

200 psi

200 psi

200 psi

P1-04

Start Level

-10.0 psi

-10.0 psi

-10.0 psi

P9-01

Lead Drive Select

2

2

2

P9-02

Feedback Source

2

2

2

P9-07

Lag Fixed Spd Dly

(PM Pump will shut off after 20 sec)

20 sec

5 sec

5 sec

P9-20

Allow Net Run

(PM Pump will be lead Pump to start)

2

0

0

P9-21

Run Priority

7

8

8

P9-24

Lead Swap @ Sleep

0 sec

1 sec

1 sec

P9-25

Highest Node Address

3

3

3

U1-01

Auto Setpoint

100 psi

100 psi

100 psi

Booster
Pump 1

Booster
Pump 2

Network

PM

Pump

3

p

m

u

p

Q

i

2

p

m

u

p

Q

i

iQpump 1

System

Pressure

Feedback

PM

V+
A2
AC

Tr

ansduc

er

10 HP

50 HP

50 HP

System

Pressure

Feedback

Pump 1

V+
A2
AC

Tr

ansd

uce

r

System

Pressure

Feedback

Pump 2

V+
A2
AC

Transducer