8 Geothermal Mode

24

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

Fault: Geothermal Frequency Reference/Temperature Curve Error: OPE19

„

Example: Geothermal Pump System Transducer Setup

Geothermal Mode Setup Procedure:

Refer to Geothermal Mode Setup Procedure on page 20

for steps to setup the iQpump Controller for Geothermal Mode.

Fault Display

Description

OPE19

Geothermal Set

Parameter selection is not compatible with the Geothermal Mode (b1-01 = 5) setting. Fault occurs when

b1-01 = 5 (Geothermal Mode), and one of the following is NOT set:
- b5-01 = 0 (PI Disabled)

- P1-01 = 0 (Simplex)

Check: Confirm parameter settings for b1-01, b5-01, and P1-01.

Example:

Geothermal Pump system using a temperature transducer 4 - 20 mA with a temperature range of 0 - 120 °F. The

system requires a minimum pump speed of 35 Hz. The system requires increased pump speed when the temperature
increases above 75 °F or when temperature falls below 65 °F.

60Hz

㩿㪧㪋㪄㪊㪋㪀

35Hz

㩿㪧㪋㪄㪊㪊㪀

55°F

㩿㪧㪋㪄㪊㪌㪀

65°F

㩿㪧㪋㪄㪊㪍㪀

Temperature (°F)

75°F

㩿㪧㪋㪄㪊㪎㪀

85°F

㪧㪋㪄㪊㪏㪀

Output

Temperature

Transducer

V+

A2

AC

+V

EG

iQpump

Output

V+

A2

AC

+V

EG

iQpump

Common

4-20mA

Temperature

Transducer

0-10V

Set S1-2 to OFF

O

F
F

1

2

Set S1-2 to ON

* Factory Default

O

F
F

1

2

Set parameter H3-08
Terminal A2 Signal to ‘0’
for 0 – 10V.