84

YASKAWA TM.iQp.10 Technical Manual Supplement

P9-08

<0034>

0887

Add Pump Mode
Add Pump Mode

Selects the detection method for staging a new pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>

0 ~ 3

0

Programming

P9-09



<0034>

0888

Add Freq Level
Add Freq Lvl

When P9-08 = 0 and the output frequency rises above this level for the
time set in P9-11, the lead drive will request for a new lead drive through
the iQpump Memobus Network.

When P9-08 = 2 and the output frequency rises above this level the delta
feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new lead
drive through the iQpump Memobus network.

0.0 ~

120.0 Hz

56.0 Hz

Programming

P9-10



<0034>

088A

Add Delta Level
Add Delta Lvl

When P9-08 = 1 and the delta feedback (setpoint - feedback) has exceeded
this level for the time set in P9-11, the lead drive will request for a new
lead drive through the iQpump Memobus Network.

When P9-08 = 2 and the delta feedback (setpoint - feedback) has exceeded
this level and the output frequency is above P9-09 for the time set in P9-11,
the lead drive will request for a new lead drive through the iQpump
Memobus network.

0 ~ 6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P9-11



<0034>

088A

Add Delay Time
Add Dly Time

Delay time before a new lead drive is added to the system.

0 ~ 3600

sec

10 sec

Programming

P9-12

<0034>

088B

Remove Pump Mode
Remove Pump Mode

Selects the detection method for de-staging to the previous lead pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>

0 ~ 3

0

Programming

P9-13



<0034>

088C

Remove Freq Level
Remove Freq Lvl

When P9-12 = 0 and the output frequency drops below this level for the
time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.

When P9-12 = 2 and the output frequency drops below this level and the
delta feedback (feedback - setpoint) has exceeded the level set in P9-14 for
the time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.

0.0 ~

120.0 Hz

40.0 Hz

Programming

P9-14



<0034><0034

>

088D

Remove Delta Level
Remove Delta Lvl

When P9-12 = 1 and the delta feedback (feedback - setpoint) has exceeded
this level for the time set in P9-15, the lead drive will request to be
removed from the system through the iQpump Memobus network.

When P9-12 = 2 and the delta feedback (feedback - setpoint) has exceeded
this level and the output frequency is below P9-13 for the time set in P9-
15, the lead drive will request to be removed from the system through the
iQpump Memobus network.

0 ~ 6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P9-15



<0034>

088E

Remove Delay Time
Remove Dly Time

Delay time before the lead drive is removed from the system.

0 ~ 3600

sec

10 sec

Programming

P9-16



<0034>

088F

Stabilization Time
Stabilization Time

Time used to stabilize the system when a pump is staged or de-staged.
Lead-lag control and pump protection is suspended during this time.

0 ~ 3600

sec

3 sec

Programming

 Denotes that parameter can be changed when the drive is running.

P9-17



<0034>

0890

Setpoint Modifier
Set-pt Modifier

System Set-point is incremented with this value depending on the number
of pumps running.
Pump 1: Set-point
Pump X: Set-point + {(X-1) (P9-17)}

-6000.0 ~

6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P9-18



<0034>

0891

High Feedback Quick De-
Stage
High FB De-stage

Determines the feedback level to trigger a quick de-stage, set as a
percentage of parameter P1-09. The quick de-stage ignores parameters P9-
12 to P9-15 and only uses an internal 2 second delay.

0.0 ~

100.0 %

90.0 %

Programming

P9-19



0892

Alternation Unit
Alternation Unit

Selects the unit for P9-03

0: Hours (hr)
1: Minutes (min)

0 ~ 1

0

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location