8 Geothermal Mode

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

21

‹

Related Parameters

„

b1-01 Frequency Reference Source Selection

Set the frequency reference source (b1-01) to 5 for Geothermal mode operation.

„

H3-09 Multi-function Analog Input Setting: Geothermal Temperature

Program H3-09 = 20 to use an external temperature sensor in Geothermal mode operation.

„

Geothermal Mode Frequency/Temperature Characteristic

When the iQpump Controller is set to operate in Geothermal Mode (b1-01 = 5), the drive's frequency reference is
determined by the analog input Geothermal Temperature (H3-09 = 20) and the setting of parameters P4-33 ~ P4-38. The
Geothermal characteristic can be programmed in normal or inverse operation.

Normal Operation: P4-33 < P4-34 and P4-35 < P4-36 < P4-37 < P4-38

Inverse Operation: P4-33 > P4-34 and P4-35 < P4-36 < P4-37 < P4-38

P4-31 Minimum Geothermal Temperature Input

P4-32 Maximum Geothermal Temperature Input

Setting

Description

0

Operator - Digital preset speed d1-01 (factory default)

1

Terminals - Analog input Terminal A1 (or Terminal A2, see parameter H3-13)

2

Serial Com - RS-485 terminals R+, R-, S+ and S-

3

Option PCB - Option board connected at 2CN

5

Geothermal Mode - Frequency reference is dependent on temperature input
(H3-09 = 20) <0035>

Setting

Description

20

Geothermal Temperature

Analog input function for use with an external temperature sensor.
Range scaling: 0V (or 4 mA) = P4-31 ~ 10 V (or 20 mA) = P4-32

Range

Description

Default

-110.0 ~ 440.0 °F

Sets the temperature that corresponds to a 0V (or 4 mA) analog input.

0.0 °F

Range

Description

Default

-110.0 ~ 450.0 °F

Sets the temperature that corresponds to a 10V (or 20 mA) analog input.

150.0 °F