13 Transducer Wiring using an External Power Supply

50

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

‹

Triplex System: Transducer Connection using Analog Input A1

A2 used for pressure transducer.

Output

Last drive on network

4-20mA

Transducer

V+

A1

AC

EG

AC

A1

EG

A1

AC

+V

EG

250

iQpump 1

iQpump 2

iQpump x

Resistor 250 Ohm / 1% 1W
Refer to Page 242 of the
TM.iQp.06 User Manual for
gain and bias settings.

*

*

+ -

External

24Vdc Power Supply