7 Suction Control via Constant Pressure w/Well Draw Down

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

17

P8-05 Wake-Up Suction Pressure

P8-06 Suction Control Minimum Speed

P8-07 Low Suction Pressure Detection Level <1>

P8-08 Low Suction Pressure Detection Time

<1>

P8-09 Water Level/Suction Pressure Selection

Sets how the drive will respond when the water level in the well drops below the P8-07 level for more than the P8-08
time.

P8-10 Suction Control Proportional Gain

P8-11 Suction Control Integral Time

P8-12 Suction Control Auto-Restart Time

Range

Description

Default

0.0 - 1200.0 psi

If the drive is forced to sleep based upon the minimum suction pressure

(P8-04), the suction pressure must go above this level for more than the P8-13
time in order to wake up.

30.0 psi

Range

Description

Default

0.00 - 120.00 Hz

This parameter sets the minimum speed the drive will run when the drive is

controlling suction pressure. When the drive is controlling outlet pressure or
this parameter is set less than P1-06 and P4-05, P1-06 and P4-05 will be used as

the minimum speed.

0.00 Hz

Range

Description

Default

0.0 - 1200.0 psi

When the amount of suction pressure drops below this level for more than the
P8-08 time, the drive will respond depending on the P8-09 setting. A setting of

0.0 disables this detection.

0.0 psi

<1>

Low Level/Low Suction Detection (P8-07/P8-08): This feature is disabled when the drive is in Run-Stop control

(b1-02 = 5, Timed Run).

Range

Description

Default

0.0- 300.0 min

Sets the amount of time delay that the suction pressure must drop below the

P8-07 level before the drive will react. *Time units are defined by P8-14.

0.1 min

Setting

Description

0

No Display (Digital Output Only)

1

Alarm Only (factory default)

2

Fault

3

Auto-Restart (time set by P8-12) (New)

Range

Description

Default

0.00 - 25.00

Sets the proportional gain for the suction pressure control.

2.00

Range

Description

Default

0.0 - 360.0 sec

Sets the integral time for the suction pressure control. A setting of zero disables

the suction pressure control integrator.

5.0 min

Range

Description

Default

0.1 - 6000.0 min

Sets the amount of time the drive will wait before attempting an auto-restart of

the "Low Suction" fault. Effective only when P8-09 = 3 and L5-01 > 0.

5.0 min