YASKAWA TM.iQp.10 Technical Manual Supplement

83

zP8-10



<0034>

869

Level Control Proportional
Gain
Lvl Ctrl P Gain

Sets the proportional gain for the water level control.

0.00 ~

25.00

2.00

Programming

„P8-10



<0035>

869

Suction Control
Proportional Gain
Suction P Gain

Sets the proportional gain for the suction pressure control.

0.00 ~

25.00

2.00

Programming

zP8-11



<0034>

86A

Level Control Integral
Time
Lvl Ctrl I Time

Sets the integral time for the water level control. A setting of zero disables
the water level control integrator.

0.0 ~

360.0 sec

5.0 sec

Programming

„P8-11



<0035>

86A

Suction Control
Integral Time
Suction I Time

Sets the integral time for the suction pressure control. A setting of zero
disables the suction pressure control integrator.

0.0 ~

360.0 sec

5.0 sec

Programming

zP8-12

<0034>

86B

Water Level Control
Auto-Restart Time
WtrLvl Restart

Sets the amount of time the drive will wait before attempting to auto-restart
of the “Low Water Level” fault. Effective only when P8-09 = 3 & L5-
01>0.

0.1 ~

6000.0 min

5.0 min

Programming

„P8-12

<0035 only>

86B

Suction Pressure Auto-
Restart Time
Suction Restart

Sets the amount of time the drive will wait before attempting to auto-restart
of the “Low Suction” fault. Effective only when P8-09 = 3 & L5-01>0.

0.1 ~

6000.0 min

5.0 min

Programming

zP8-13

<0034>

86C

Water Level Control
Sleep Wake-up Time
WL Wake-up Time

If the drive has been forced to sleep based upon the minimum water level
(P8-04), the water must go above the P8-05 level for more than this time in
order to wake up.

0.0 ~

3600 sec

1 sec

Programming

„P8-13

<0035 only>

86C

Suction Pressure
Sleep Wake-up Time
SP Wake-up Time

If the drive has been forced to sleep based upon the minimum suction
pressure (P8-04), the pressure must go above the P8-05 level for more than
this time in order to wake up.

0.0 ~

3600 sec

1 sec

Programming

zP8-14

<0034>

86D

Low Water Level
Detection Time Unit
Low Lvl Det Unit

Defines the time unit for P8-08.
0: Minutes (min)
1: Seconds (sec)

0 ~ 1

0

Programming

„P8-14

<0035 only>

86D

Low Suction Pressure
Detection Time Unit
Low Pres Det Unit

Defines the time unit for P8-08.
0: Minutes (min)
1: Seconds (sec)

0 ~ 1

0

Programming

Network Options

Parameter functionality stated below only applies when P1-01 = 3 (Memobus Network)

P9-01

<0034>

0880

Lead Drive Selection
Lead Drive Sel

Specifies how the next Lead Drive is selected.
0: Next Available
1: Lowest Runtime
2: Stop History <0035>

0 ~ 2

1

Programming

P9-02

<0034>

0881

Feedback Source
Feedback Source

Defines which signal to use for PI Feedback when P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alarm.
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01 = 3.

0 ~ 3

0

Programming

P9-03



<0034>

0882

Alternation Time
Alternation Time

Specifies the time for a drive to request alternation, influenced by the
Alternation Mode P9-04.
The alternation feature is disabled when this parameter is set to 0.

0 ~ 1000 hr

24 hr

Programming

 Denotes that parameter can be changed when the drive is running.

P9-04

<0034>

0883

Alternation Mode
Alternation Mode

Determines how alternation is performed:
0: FIFO Auto
1: FIFO Forced
2: LIFO

0 ~ 2

0

Programming

P9-05

<0034>

0884

Lag Drive Mode
Lag Drive Mode

Determines how the lag drives function.
0: Fixed Speed - Runs at the P9-06 setting.
1: PI Regulation - Uses PI to determine speed.
2: Turn Off: Drive stops running when it switches to a lag drive after the
P9-07 time expires.
3: Follow Lead Spd: The drive will follow the speed of the current Lead
drive applying P9-30 gain and P9-31 bias. <0035>

0 ~ 3

0

Programming

P9-06



<0034>

0885

Lag Fixed Speed
Lag Fixed Speed

When the drive changes from a lead to a lag and P9-05 = 0, the drive will
run at this speed after P9-07 delay time expires.

0.0 ~

120.0 Hz

55.0 Hz

Programming

P9-07



<0034>

0886

Lag Fixed Speed Delay
Lag Fixed Spd Dly

When the drive changes from a lead to a lag and P9-05

1, this time

specifies how long the speed is latched before doing one of the following:
<0035>
(1) P9-05 = 0: Run at P9-06
(2) P9-05 = 2: Turn off
(3) P9-05 = 3: Follow the Lead Drive’s speed.

0 ~ 1000

sec

5 sec

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location