8 Geothermal Mode

22

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

Figure 4

Figure 4 Digital Operator Display Showing Geothermal Mode Operation

Parameter No.

Parameter Name

Description

Range

Default

P4-33

Minimum Geothermal Speed

Sets the frequency reference characteristics based on the set
temperature points and the corresponding frequency.

For proper operation, P4-34 > P4-33 and P4-38 > P4-37 > P4-36 >
P4-35.

Geothermal Mode Frequency/Temperature Characteristic|
(Normal Operation)

.

Geothermal Mode Frequency/Temperature Characteristic
(Inverse Operation)

0.00 ~
120.00 Hz

40.00 Hz

P4-34

Maximum Geothermal Speed

0.00 ~
120.00 Hz

40.00 Hz

P4-35

Low Temperature to Run at
Maximum Geothermal Speed

-110.0 ~
450.0 °F

55.0 °F

P4-36

Low Temperature to Run at
Minimum Geothermal Speed

-110.0 ~
450.0 °F

65.0 °F

P4-37

High Temperature to Run at
Minimum Geothermal Speed

-110.0 ~
450.0 °F

75.0 °F

P4-38

High Temperature to Run at
Maximum Geothermal Speed

-110.0 ~
450.0 °F

85.0 °F

Maximum

Geothermal Speed

㩿㪧㪋㪄㪊㪋㪀

Minimum

Geothermal Speed

㩿㪧㪋㪄㪊㪊㪀

Low Temp

@ Max
㩿㪧㪋㪄㪊㪌㪀

Low Temp

@ Min

㩿㪧㪋㪄㪊㪍㪀

Temperature (°F)

High Temp

@ Min

㩿㪧㪋㪄㪊㪎㪀

High Temp

@ Max
㩿㪧㪋㪄㪊㪏㪀

Maximum

Geothermal Speed

㩿㪧㪋㪄㪊㪋㪀

Minimum

Geothermal Speed

㩿㪧㪋㪄㪊㪊㪀

Low Temp

@ Max
㩿㪧㪋㪄㪊㪌㪀

Low Temp

@ Min

㩿㪧㪋㪄㪊㪍㪀

Temperature (°F)

High Temp

@ Min

㩿㪧㪋㪄㪊㪎㪀

High Temp

@ Max
㩿㪧㪋㪄㪊㪏㪀