YASKAWA TM.iQp.10 Technical Manual Supplement

89

U1-91

0721

Pump Feedback
Pump Feedback

Displays scaled feedback.
Resolution 0.1

U1-92

0722

Pump Status
Pump Status

Display pump running status.

U1-93

723

Total Set-point Compensation
Total SP Comp.

Displays total absolute setpoint compensation.
Resolution 1.

U1-94

724

Motor Speed
Motor Speed

Displays motor speed (rpm).
Used for no-flow detection (P2 Group).

U1-95

725

Flow Rate
Flow Rate

Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01
and P6-02. A two second 1st order filter will be applied to this monitor.

U1-96

72A

Volume Accumulated
(fine)
Volume (fine)

Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.

U1-97

72B

Volume Accumulated
(course)
Volume (course)

Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.

zApplies when P8-01 = 0 or 1

„Applies when P8-01 = 2

zU1-98

72C

Water Level
Water Level

Displays the amount of water above the water level sensor.

„U1-98

<0035>

72C

Water Level
Suction Pressure

Displays the amount of suction pressure.

U1-99

72D

Anti-No-Flow Timer
ANF Timer

When this value reaches the P2-24 setting, the Anti-No-Flow feature begins to reduce the
output frequency.

Parameter No.

Addr.

Hex

Parameter Name Digital

Operator Display

Description

Monitor

0 0 0 0 0 0 0 0

1: Drive (Pump 1)

1: Pump 2 on

1: Pump 3 on

Not used. Always 0.