YASKAWA TM.iQp.10 Technical Manual Supplement

65

H5-03

0427

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for Terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note: Drive power must be cycled before the changes will take effect.

<0034>

0 ~ 2

0

Programming

H5-04

0428

Stopping Method after
Communication Error
Serial Flt Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

3

Programming

H5-05

0429

Communication Error
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a communications
fault.
1: Enabled - If communications are lost for more than the time specified in
parameter H5-09, a communications fault will occur.

0 ~ 1

1

Programming

H5-06

042A

Drive Transmit Wait Time
Transmit WaitTim

Sets the time from when the drive receives data to when the drive sends
data.

5 ~ 65 ms

5 ms

Programming

H5-07

042B

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:

0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 ~ 1

1

Programming

H5-08

042C

Communication Protocol
Selection
Com Protocol Sel

0: MEMOBUS/Modbus
1: N2 (Metasys)
2: FLN (APOGEE)

0 ~ 2

0

Programming

H5-09

0435

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.

0.0 ~

10.0 sec

2.0 sec

Programming

Motor Overload

L1-01

0480

Motor Overload Protection
Selection
MOL Flt Sel

Enables or disables the motor thermal overload protection.

0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

0 ~ 1

1

Programming

L1-02

0481

Motor Overload Protection
Time
MOL Time Const

Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10 %. Actual (OL1) trip time will vary depending on severity of overload.

0.1 ~

20.0 min

8.0 min

Programming

L1-03

0482

Motor Overheat Alarm
Operation Selection
Mtr OH Alarm Sel

Operation selection when the motor temperature analog input

(H3-09 = E) exceeds the OH3 alarm level (1.17 V)

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

3

Programming

L1-04

0483

Motor Overheat Fault
Operation Selection
Mtr OH Fault Sel

Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 ~ 2

1

Programming

L1-05

0484

Motor Temperature Input
Filter Time
Mtr Temp Filter

Delay Time applied to motor temperature analog input (H3-09 = E) for
filtering purposes.

0.00 ~

10.00 sec

0.20 sec

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu