7 Suction Control via Constant Pressure w/Well Draw Down

18

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

P8-13 Suction Pressure Sleep Wake-Up Time

P8-14 Low Suction Pressure Detection Time Unit

Defines the time unit for P8-08.

Suction Pressure Transducer Wire-break Detection

Wire-break detection is active on Terminal A1 when PI Feedback Loss Detection is enabled (b5-12 = 1 or 2) , Suction
control is enabled (P8-01 = 2) and PI control is NOT disabled via Multi-Function Digital Input.

The iQpump Controller detects a wire-break condition when the suction transducer signal on Terminal A1 falls below -
6.25 % or rises above 106.25 % for more than 1 second and will react according to parameter b5-12 (Feedback Loss
Detection).

Note: Wire-break detection on Terminal A1 detection is checked after the gain/bias parameters (H3-02 and H3-03) are applied.

Fault: Low Suction

Parameters P8-12 to P8-14 are also available for Water Level control P8-01 set to 1. The parameter titles change
accordingly.

P8-12 Water Level Auto-Restart Time

P8-13 Water Level Sleep Wake-Up Time

P8-14 Low Water Detection Time Unit

Multi-function Output Setting H2-††: Low Suction (Modified)

Range

Description

Default

0 - 3600 sec

If the iQpump Controller has been forced to sleep based upon the minimum

suction pressure (P8-04), the pressure must go above the P8-05 level for more
than this time in order to wake up.

1 sec

Setting

Description

0

Minutes (factory default)

1

Seconds

Fault Display

Description

LOSUC

Low Suction

Low Suction: Suction pressure is below the P8-07 level for more than the P8-08 time.

Range

Description

Default

0.1 - 6000.0 min

Sets the amount of time the iQpump Controller will wait before attempting an

auto-restart of the "Low Water" fault. Effective only when P8-09 = 3 and
L5-01 > 0.

5.0 min

Range

Description

Default

0 - 3600 sec

If the iQpump Controller is forced to sleep based upon the minimum water
level (P8-04), the pressure must go above the P8-05 level for more than this

time in order to wake up.

1 sec

Setting

Description

0

Minutes (factory default)

1

Seconds

Setting

Description

57 Low Water

This output will energize if P8-01 = 1 and the level in the well drops below the Low Level Detection Level

(P8-07) for more than the Low Level Detection Delay Time (P8-08), or if there is a LOWWL - Low Water
Level Fault.