10 iQpump MEMOBUS/Network Operation

30

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

„

Related Parameters

P9-06 Lag Fixed Speed

P9-07 Lag Fixed Speed Delay

Time delay before execution of P9-05 selection when the iQpump Controller changes from lead to lag.

Note: Only active when Lag Mode Selection (P9-05) is set to 0, 2 or 3.

„

New Parameters

P9-30 Lag Follower Gain

P9-31 Lag Follower Bias

Range

Description

Default

0 - 120.0 Hz

When the drive changes from a lead to a lag and P9-05 = 0, the drive will run at

this speed after P9-07 delay time expires.

55.0 Hz

Range

Description

Default

0 - 1000 sec

When the drive changes from a lead to a lag and P9-05

≠ 1, this time specified

in parameter P9-07 determines how long the speed is latched before executing
one of the following operations:

1. P9-05 = 0: Run at P9-06
2. P9-05 = 2: Turn off
3. P9-05 = 3: Follow the Lead Drive's speed.

5 sec

Range

Description

Default

0.0 -300.0%

When P9-05 = 3, the drive will follow the speed of the active lead drive

applying this gain and P9-31 bias to the reference signal.

100.0 %

Range

Description

Default

-60.00 - 60.00 Hz

When P9-05 = 3, the drive will follow the speed of the active lead drive
applying this bias and P9-30 gain to the reference signal.

0.00 Hz