YASKAWA TM.iQp.10 Technical Manual Supplement

63

H2-02

(continued)

040C

Terminal M3-M4 Function
Selection
Term M3-M4 Sel

55: Lube Pump

<0034>

Closed: When the Lube Pump Feature is active.
This will energize for the time set in parameter P4-23 each time the drive is
supposed to start. The drive will delay starting for the P4-23 time.
56: High Flow

<0034>

Closed: During the “High Flow Fault” condition. -OR-
Closed: During a high flow condition as set by P6-12 ~ P6-14 (included
“High Flow Alarm”)
57: Low Water Level

<0034>

Closed: During the “Low Water Level” condition as set by P8-07 and P8-
08. -OR-
Closed: During the LOWWL - Low Water Level Fault”.
This will energize if P8-01 = 1 and the level in the well drops below the
Low Level Detection Level (P8-07) for more than the Low Level
Detection Delay Time (P8-08), or if there is a LOWWL - Low Water Level
Fault.
58: Low Suction <0035>
This will energize if P8-01 = 2 and the suction pressure drops below the
Low Suction Pressure Detection Level (P8-07) for more that the Low
Suction Pressure Delay Time (P8-08), of if there is a LOSUC - Low
Suction Pressure Fault.

0 ~ 57

41

Programming

Analog Inputs

H3-02



0411

Terminal A1 Gain Setting
Terminal A1 Gain

Sets the speed command when 10 V is input, as a percentage of the
maximum output frequency (E1-04).

0.0 ~

1000.0 %

100.0 %

Programming

H3-03



0412

Terminal A1 Bias Setting
Terminal A1 Bias

Sets the speed command when 0 V is input, as a percentage of the
maximum output frequency (E1-04).

–100.0 ~

+100.0 %

0.0 %

Programming

H3-08

0417

Terminal A2 Signal Level
Selection
Term A2 Signal

Selects the signal level of Terminal A2.
0: 0 - 10 Vdc (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)
3: 0- 20 mA

0 or 2

2

Programming

H3-09

0418

Aux Terminal Function
Selection
Terminal A2 Sel

Selects what effect the aux terminal has on the drive.
0: Frequency Bias - 0 - 100 % bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100 % bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
20: Geothermal Mode <0035>
1F: Not Used

0 ~ 1F

B

Programming

H3-10



0419

Terminal A2 Gain Setting
Terminal A2 Gain

Sets the percentage when 10 V (20 mA) is input.

0.0 ~

1000.0 %

100.0 %

Programming

H3-11



041A

Terminal A2 Bias Setting
Terminal A2 Bias

Sets the percentage when 0 V (4 mA) is input.

–100.0 ~

+100.0 %

0.0 %

Programming

H3-12

041B

Analog Input Filter Time
Constant Filter Avg Time
Analog Input Fil Tim

Used to “smooth” out erratic or noisy analog input signals.

0.00 ~

2.00 sec

0.30 sec

Programming

H3-13

041C

Master Frequency
Reference
Terminal Sel TA1/A2
Select

Determines which terminal will be the main reference source.
0: Main Fref TA1 - Terminal TA1 is the main speed command and
Terminal TA2 is the Aux speed command.
1: Main Fref TA2 - Terminal TA2 is the main speed command and
Terminal TA1 is the Aux speed command. Only effective when H3-09 is
set to 2 “Aux Reference”.

0 ~ 1

0

Programming

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location