YASKAWA TM.iQp.10 Technical Manual Supplement

73

P2-02



060B

Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed sleep
level for time specified in P2-03. The level type is determined by
P2-01. A value of 0 disables this function. This function is only active
during running while operating in auto mode.
If P1-01 = 3, the function is active when there is only one drive running on
the network.

<0034>

Display Units for Sleep Level P2-02 when P2-01 is programmed for the
following:
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “A”
P2-01=2: Display based on P1-02 Selection
P2-01=3: Display based on “rpm”

<0034>

P2-01=4: Display based on P6-02 Selection

<0034>

Note: When P2-01 is set for a value of 2, display units will be dependent
on P1-02 setting. If P2-02 = 0, pump will sleep at minimum speed.

0.0 ~

6000.0

0.0

Programming

P2-03



060C

Sleep Delay Time
Sleep Delay Time

Delay time before drive enters sleep mode when criteria is met as defined
by parameter P2-02.

0 ~ 3600

sec

5 sec

Programming

P2-04



060D

Delta Sleep Feedback
Drop Level
D Fb Drop Level

When the drive enters sleep mode, the software monitors the feedback to
detect a flow-no flow condition. If the PID Error (setpoint minus feedback)
exceeds the programmed level P2-04 within the programmed time (P2-05)
and the output frequency is greater than the minimum frequency (P1-06),
the sleep operation deactivates and the drive returns to normal operation. A
value of 0 disables this function.

0.0 ~

6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P2-05



060E

Feedback detection drop
time.
FB Drop DetTime

Defines the time window in which the software monitors the feedback to
detect a flow-no flow condition. Works in conjunction with parameter P2-
04.

0 ~ 3600

sec

10 sec

Programming

P2-06



060F

Sleep Mode: Cycling
Protection
Cycle Protection

Maximum number of cycles allowed within the time specified in P2-07
before the drive initiates a “Pump Cycle Fault (PCF)”. One Cycle is
defined when the drive transfers from normal operation in auto mode to
sleep mode. A value of 0 disables this function.
If P1-01 = 3, the function is active when there is only one drive running on
the network.

<0034>

0 ~ 10

0

Programming

P2-07



0610

Sleep Mode: Maximum
Cycling Protection Time
Max. Cycle Time

Maximum time allowed between cycles. When no cycling occurs within
the programmed time, the drive will reset the internal cycle register. Works
in conjunction with P2-06.

0 ~ 3600

sec

300 sec

Programming

P2-08

0611

Over Cycling Mode
Over Cycle Mode

Sets the Over Cycle Mode:
0: Disabled
1: Alarm
2: Pump Over Cycle Fault (POC)
3: Auto Compensation

0 ~ 3

0

Programming

P2-09

0612

Set-point Compensation
Set-point Comp

Allows for the software to automatically compensate the setpoint in case of
excessive cycling.

0.0 ~

6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P2-10

0613

Maximum Set-point
Compensation
Max. SP Comp

Maximum allowable setpoint compensation for the over-cycling function.

0.0 ~

6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Pump Quick

Setup

P2-11

010B

No-Flow Activation Level
NF Act. Level

When the motor rpm falls below the programmed level in P2-12, the no-
flow detection will activate. A value of 0 disables this function.
If P1-01 = 3, the function is active on the lead drive.

<0034>

0 ~

24000 rpm

0 rpm

Programming

P2-12

010C

No-Flow Detection
Bandwidth
NF Det.Bandwidth

Sets the motor rpm fluctuation bandwidth. No-flow activates when the
motor rpm remains within the programmed bandwidth in P2-12 for a time
specified in parameter P2-13.

0 ~

1000 rpm

15 rpm

Programming

P2-13

010D

No-Flow Detection Time
NF Detect Time

No-flow activates when the motor rpm remains within the programmed
bandwidth (P2-12) for a time specified in parameter
P2-13.

0.0 ~

1000.0 sec

5.0 sec

Programming

P2-14

010E

No-Flow Stabilization
Time
NF StabilizeTime

Time delay when setpoint returns to the original setting after being
changed for no-flow detection.

0.0 ~

1000.0 sec

5.0 sec

Programming