5 Feature Details - Remote Drive Disable

12

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

Figure 2

Figure 2 Remote Disable: Active to Inactive Operation

P4-25 Remote Drive Disable On-Delay Time

P4-26 Remote Drive Disable Off-Delay Time

Multi-function Input Setting: Remote Drive Disable Function

Alarm: Remote Drive Disable

Note: S† or Sx denotes the digital input terminal programmed for this function.

Range

Description

Default

1 - 1000 sec

Sets the amount of time a “Remote Drive Disable” condition needs to be

present before the drive will stop.

0 sec

Range

Description

Default

1 - 1000 sec

Sets the amount of time a "Remote Drive Disable" condition must be absent
before the drive will be allowed to run.

0 sec

Setting

Description

72 Remote Drv Disbl

Remote Drive Disable: Prevents the iQpump Controller from running when active for the time set in

P4-25. Must be inactive for the time set in P4-26 to allow the drive to run again.
Note: Parameter P4-24 determines if this input is Normally Open or Normally Closed.

Alarm Display

Description

R-DNE-Sx

Remote Drv Dis

Multi-function Input Terminal S† (H1-0† = 72) has been closed for the time set in P4-25 when P4-24 = 0.

or
Multi-function Input Terminal S† (H1-0† = 72) has been open for the time set in P4-25 when P4-24 = 1.

iQpump Drive Enabled

iQpump Drive Stopped

Time

Remote

Drive Disable

Active

P4-26 Off-Delay Time

Inactive