YASKAWA TM.iQp.10 Technical Manual Supplement

81

P6-10



<0034>

849

Accumulation Level
Course
Accum Lvl Course

Sets the accumulated volume that will trigger the Accum Level alarm.
Accum Level fault, or Accum Level digital output. Total Accum Level can
be calculated as follows:
Total Accum Level = P6-10 x 1000 + P6-09.
If P1-01 = 3, an ACCUM fault will stop all drives running on the network.

0 ~

61036 kgl

0 kgl

Programming

P6-11



<0034>

84A

Accumulation Behavior
Accum Behavior

Sets how the drive will respond when the accumulated volume reaches the
P6-09 and P6-10 level.
0: No Display
1: Alarm Only
2: Fault
3: Fault - Auto Flow Accum Reset

0 ~ 3

1

Programming

P6-12



<0034>

84B

High Flow Level
High Flow Level

If the drive is running and the flow goes above this level for more than the
P6-13 time, a High Flow fault or alarm will occur.
A setting of 0 disables the High Flow detection.
If P1-01 = 3, a HIFLO fault will stop all drives running on the network.

0.0 ~

6000.0

(*n1)

0.0

Programming

P6-13



<0034>

84C

High Flow Detection
Delay Time
High Flow Time

Sets the amount of time the flow rate must be above the P6-12 level before
a High Flow condition is detected.

1 ~ 6000

sec

10 sec

Programming

P6-14

<0034>

84D

High Flow Select
High Flow Sel

Sets the behavior of the drive when a “High Flow” condition is detected.
0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by L5-03)

0 ~ 3

1

Programming

(*n1) Displayed units are determined by parameter P6-02.

Anti-Jam/De-Scale

P7-01

<0034>

84F

Anti-Jam/De-Scale
Operation Selection
Anti-Jam/De-Scale

Selects if the Anti-Jam or De-Scale functions are enabled.
0: Disabled
1: Anti-Jam Enabled
2: De-Scale Enabled.
3: Force De-Scale

0 ~ 3

0

Programming

P7-02



<0034>

850

Anti-Jam/De-Scale Cycle
Count
A-J Cycle Count

This parameter sets the maximum number of cycles attempted before the
Anti-Jam fault occurs and also sets the number of fwd/rev cycles for the
De-Scale function.

1 ~ 100

1

Programming

P7-03



<0034>

851

Anti-Jam Detection
Current Level
A-J Detection Level

Sets the current level (at start) that will trigger the Anti-Jam function. Set
as a percentage of motor rated current.

50 ~ 200 %

120 %

Programming

P7-04



<0034>

852

Anti-Jam Detection Time
A-J Det. Time

Sets the amount of time the current must be above the P7-03 level to
trigger the Anti-Jam function.

0.1 ~ 2.0

sec

0.3 sec

Programming

P7-05



<0034>

853

Anti-Jam/De-Scale
Frequency Reference
AJ/De-Scale Freq

Sets the speed during the De-Scale operation and during reverse operation
of the Anti-Jam function.

0.00 ~

120.00 Hz

25.00 Hz Programming

P7-06



<0034>

854

De-Scale Forward Run
Time
De-Scale Fwd Run

Sets the amount of time the drive will run in the forward time each cycle
during the De-Scale function.

1 ~ 6000

sec

10 sec

Programming

P7-07



<0034>

855

De-Scale Reverse Run
Time
De-Scale Rev Run

Sets the amount of time the drive will run in the reverse time each cycle
during the De-Scale function.

1 ~ 6000

sec

10 sec

Programming

 Denotes that parameter can be changed when the drive is running.

P7-08



<0034>

856

De-Scale Acceleration
Time
De-Scale Accel

Sets the amount of time it will take the drive to accelerate from zero to the
De-Scale frequency reference P7-05 (internally limited 0.1 ~ 6000.0 sec).

0.0 ~

600.0 sec

2.0 sec

Programming

P7-09



<0034>

857

De-Scale Deceleration
Time
De-Scale Decel

Sets the amount of time it will take the drive to decelerate from the
De-Scale frequency reference P7-05 to zero (internally limited 0.1 ~
6000.0 sec).

0.0 ~

600.0 sec

2.0 sec

Programming

P7-10



<0034>

858

De-Scale Pump Run Time
De-Scale Time

Sets the number of pump operating hours (pump speed > 0) before a
De-Scale routine will run.

1.0 ~

2000.0 hr

168.0 hr

Programming

P7-11



<0034>

859

Anti-Jam Release Time
Anti-Jam Release

Sets the amount of time that the current must be below the P7-03 level in
order to resume normal operation.

0.5 ~

10.0 sec

2.0 sec

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location