10 iqpump memobus/network operation, Lag drive speed follower and lag turn off, Iqpump memobus/network operation – Yaskawa iQpump Manual Supplement User Manual

Page 29

Advertising
background image

10 iQpump MEMOBUS/Network Operation

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

29

10

iQpump MEMOBUS/Network Operation

‹

Lag Drive Speed Follower and Lag Turn Off

Certain multiplex pump systems require a common pump speed for all running pumps. To allow for this operation, a new
selection "Follow Lead Spd" is added to parameter P9-05.

„

Function Description

P9-05 Lag Drive Mode

Note: The rate at which the Lag drives follow the Lead drive's output speed is dependent on the communication speed of the iQpump

Controller network (H5-02), the maximum number of iQpump Controllers on the network (P9-25) and the current number of
iQpump Controllers online.

Display Message for Follow Lead Speed Operation:

When the iQpump Controller is operating in Auto Mode, Lag operation and the Follow Lead Speed function is active
(P9-05 = 3) then the display will show the actual frequency reference in Hz instead of the selected system units.

Setting

Description

0

Fixed Speed (factory default)

Runs at the P9-06 setting after the P9-07 time expires.

1

PI Regulation.
Uses PI to determine speed.

2

Turn Off

The iQpump Controller stops running when it switches to a lag drive after P9-07 time expires.

3

Follow Lead Spd

The iQpump Controller follows the speed of the active Lead drive. Use P9-30 gain and P9-31 bias setting
to adjust reference signal.