10 iQpump MEMOBUS/Network Operation

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

33

P9-11 Add Delay Time

P9-12 Remove Pump Mode

Selects the detection method for de-staging to the previous lead pump.

P9-15 Remove Delay Time

Alarm: Network Water or Suction Pressure Signal Lost

Range

Description

Default

0 ~ 3600 sec

Delay time before a new lead drive is added to the system.

10 sec

Setting

Description

0

Output Frequency (factory default)

1

Feedback

2

Feedback + Fout

3

Flow Meter

Range

Description

Default

0 ~ 3600 sec

Delay time before the lead drive is removed from the system.

10 sec

Alarm Display

Description

Net FlowMeter
Lost, Chk Source

There is no drive on the Memobus Network with an analog Flow Meter.

Cause: With P1-01 = 3, P6-01 > 0 and P9-40 = 1 (Network), the Flow Meter function needs a valid Flow

Rate from the network originating from another drive that is also running the Flow Meter function

(P6-01 > 0) with P9-40 = 0 (Analog).

Countermeasure: If the drive has an operational Flow Meter connected to Terminal A1, set P9-40 = 0. If

another drive on the Memobus Network has a Flow meter connected to Terminal A1, confirm that drive is
online, with P6-01 > 0 and P9-40 = 0.