Improved and Miscellaneous Functions

‹

Terminal A1 Loss Detection

Feedback loss detection alarm and fault messages are enhanced to differentiate between terminal A1 feedback loss and
Terminal A2 PI feedback loss.

Use parameter b5-12 is select feedback loss detection operation for terminal A1.

„

Parameters

b5-12 Feedback Loss Detection

New Alarm Message: Feedback Loss Terminal A1 (Modified)

New Fault Message: Feedback Loss Terminal A1 (Modified)

Multi-function Output Setting: Transducer Loss (Modified)

„

Function Description Feedback Loss Detection

Wire break (feedback loss detection) will be detected on Terminal A1 when all of the following conditions are satisfied:

• PI Feedback Loss Detection is enabled (b5-12 = 1 or 2).
• PI function is enabled (b5-01 > 0).
• Dual Zone PI or Water Level/Suction Pressure Control is enabled (b5-01 = 2 or P8-01 > 0, P1-01 = 0, b5-09 = 0, and

H3-09 = B).

• PI function is NOT disabled via Multi-Function Digital Input.
• Signal on Terminal A1 falls below -6.25 % or rises above 106.25 % for more than 1 second.

Note: Wire-break detection on Terminal A1 is checked after the gain/bias parameters (H3-02 and H3-03) are applied.

Setting

Description

0

Disabled

1

Alarm

2

Fault (factory default)

Fault Display

Description

A1-LOST
Terminal A1 Lost

Shown when b5-12 = 1 and feedback signal on terminal A1 is lost. Check to ensure the device connected to
Terminal A1 is installed and working properly.

Fault Display

Description

A1-LOST

Terminal A1 Lost

Shown when b5-12 = 2 and feedback signal on terminal A1 is lost. Check to ensure the device connected to

Terminal A1 is installed and working properly.

Setting

Description

4A

Transducer Loss

Closed: During a "Feedback Loss" alarm.

Closed: During a "FBL - Feedback Loss" fault".
Closed: During an "A1-LOST Terminal A1 Lost" alarm (New)

Closed: During an "A1-LOST Terminal A1 Lost" fault (New)