YASKAWA TM.iQp.10 Technical Manual Supplement

85

P9-20

0893

Allow Network Run
Allow Net Run

Specifies when a network run command is allowed:
0: Always
1: First/Alternation
2: First Only
3: Alternation Only

0 ~ 3

0

Programming

P9-21



0894

Run Priority
Run Priority

Sets the Lead Drive selection priority overriding the P9-01 selection. If
multiple drives have the lowest P9-21 value, then P9-01 determines which
drive becomes the Lead.

1 ~ 16

8

Programming

P9-22



<0034>

0895

System Fault Retry
System Flt Retry

Determines the number of times the iQpump Memobus Network will allow
automatic restarts of system faults. The drive uses parameter
L5-03 in determining when to attempt a system fault restart.
For proper operation, this parameter should be set the same for all network
drives.

0 ~ 10

5

Programming

P9-23



<0034>

0896

Max Number of Running
Pumps
MaxPumps Running

Limits the maximum number of pumps that can run on the system.

1 ~ 8

8

Programming

P9-24



<0034>

0897

Lead Swap @ Sleep
Lead Swap @ Sleep

When the Lead DRive has been in Sleep for this amount of time and there
is another drive available with a lower P9-21, then this drive will request
for a swap.
A setting of 0 disables this function.

0 ~ 7200

sec

0 sec

Programming

P9-25

<0034>

0898

Highest Node Address
Highest Node Adr

Defines the highest possible node address in the Memobus network. To
yield optimal network performance, it is recommended to set the serial
communication address H5-01 starting from 01h and then consecutively up
to the last drive and then setting this parameter to that H5-01 address.

02h ~ 8h

08 h

Programming

P9-26

<0034>

0899

Master Time-Out
Master Time-0ut

Sets the minimum amount of time that the slave drives will wait for a
message from the master before performing the action set in P9-27.

3.0 ~

10.0 sec

4.0 sec

Programming

P9-27

<0034>

089A

Network Recovery
Network Recovery

When no messages are received from the master for the time set in
P9-26, the slave drive will act according to this setting:
0: Automatic - drive will attempt to assume master functionality.
1: Slave/Resume - drive will continue running when the master is lost and
will wait for a master to come on-line.
2: Slave/Stop - drive will stop running when the master is lost and will wait
for a master to come on-line.
3: Fault MSL - fault the drive with an MSL (Master Lost).

0 ~ 3

0

Programming

P9-28

<0034>

089B

NETSCAN Alarm Time
NETSCAN Alrm Time

Sets the amount of time that the slave drives will wait for a message from
the master before displaying a NETSCAN alarm.

1.0 ~

10.0 sec

2.0 sec

Programming

P9-29



<0034>

089C

Net Start Delay
Net Start Delay

After the first drive on the network has been put on Auto mode, the
network will wait this amount of time before selecting and starting the
Lead Drive.

0.0 ~

60.0 sec

2.0 sec

Programming

P9-30



<0035>

0876

Lag Drive Speed
Follower Gain
Lag Follower Gain

When P9-05 = 3, the drive will follow the speed of the current lead drive
applying this gain and the P9-31 bias.

0.0 ~

300.0%

100.0%

Programming

P9-31



<0035>

0877

Lag Drive Speed
Follower Bias
Lag Follower Bias

When P9-05 = 3, the drive will follow the speed of the current lead drive
applying the P9-30 gain and this bias.

-60.0 ~
60.0Hz

0.00Hz

Programming

P9-32



<0036>

0871

Lag Follower
Deceleration Time
Lag Follower Dcel

When the P9-33 timer is running, and the drive is running as Lag Drive
Speed Follower (P9-05 = 3), then the deceleration time is set to this value.

0.0 ~

1000.0 sec

60.0 sec

Programming

P9-33



<0036>

0872

Lag Follower
Deceleration Time Active
Time
Lag Follower Dtim

The P9-32 deceleration time is effective during this time window. The
drive will use the standard deceleration rates when it expires.

A setting of 0.0 sec will disable the Lag Follower deceleration time
switching.

0.0 ~

360.0 sec

0.0 sec

Programming

P9-40



<0035>

089D

Flow Rate Source
Flow Rate Source

Defines the Flow Meter input source when P1-01=3:
0: Analog
1: Network

0 ~ 1

0

Programming

P9-41



<0035>

089E

Add Flow Rate Level
Add Flow Lvl

When P9-08=3 and the Flow Rate is above this level x no. of pumps
running for the time set in P9-11, the lead drive will request for a new lead
drive through the iQpump Memobus network.
Note: (*n1) Displayed units are determined by parameter P6-02.

0.0 ~

6000.0

(*n1)

0

Programming

P9-42



<0035>

089F

Remove Flow Rate Level
Remove Flow Lvl

When P9-12=3 and the Flow Rate is above this level x (no. of pumps
running -1) for the time set in P5-15, the lead drive will request to be
removed from the system through the iQpump Memobus network.
Note: (*n1) Displayed units are determined by parameter P6-02.

0.0 ~

6000.0

(*n1)

0

Programming

zApplies when P8-01 = 0 or 1

„Applies when P8-01 = 2

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location