YASKAWA TM.iQp.10 Technical Manual Supplement

o1-07

0518

Second Line User Monitor
Selection
2nd Monitor Sel

Sets the “U1” monitor always displayed on the 4th line of the digital
operator display. Effective only when o1-06 = 1.

1 ~ 94

2

Programming

o1-08

0519

Third Line User Monitor
Selection
3rd Monitor Sel

Sets the “U1” monitor always displayed on the 5th line of the digital
operator display. Effective only when o1-06 = 1.

1 ~ 94

91

Programming

Key Selections

o2-01

0505

Local/Remote Key
Function Selection
Local/Remote Key

Has no function when HOA operator is connected.
0: Disabled
1: Enabled

0 ~ 1

1

Programming

o2-02 0506

OFF Key Function During
Auto Run
Oper OFF Key

Determines if the off key on the digital operator will stop the drive when
drive is operating from external terminals or serial communications.
0: Disabled
1: Enabled

0 ~ 1

1

Programming

o2-03

0507

User Parameter Default
Value
User Defaults

Allows storing of current parameter values as a User Initialization
Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user initialization. A1-
03 now allows selecting <1110> for user initialization.
2: Clear All (Clears the currently saved user initialization. A1-03 no longer
allows selecting <1110>.

0 ~ 2

0

Programming

o2-04

0508

Drive/kVA Selection
Inverter Model #

Sets the kVA of the drive. Enter the number based on drive model #. Use
the †††† portion of the CIMR-P7††††-107 Model Number.

0 ~ FF

kVA

Dependent

Programming

o2-05

0509

Frequency Reference
Setting
Method Selection
Operator M.O.P.

Determines if the Data/Enter key must be used to input a frequency
reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency
reference.
1: Enabled: -Data/Enter key is not required. The frequency reference is
adjusted by the up and down arrow keys on the digital operator without
having to press the data/enter key.

0 ~ 1

0

Programming

o2-06

050A

Operation Selection when
Digital Operator is
Disconnected
Oper Detection

Determines if the drive will stop when the digital operator is removed.
0: Disabled - The drive will not stop when the digital operator is removed.
1: Enabled - The drive will fault (OPR) and coast to stop when the operator
is removed.

0 ~ 1

1

Programming

o2-07

050B

Cumulative Operation
Time Setting
Elapsed Time Set

Sets the initial value of the elapsed operation timer.

0 ~

65535 hr

0 hr

Programming

o2-08

050C

Cumulative Operation
Time Selection
Elapsed Time Run

Sets how time is accumulated for the elapsed timer (o2-07).
0: Power-On Time (Time accumulates whenever drive is powered).
1: Running Time (Time accumulates only when drive is running)

0 ~ 1

1

Programming

o2-10

050E

Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set

Sets the initial value of the heatsink fan operation time.

0 ~

65535 hr

0 hr

Programming

o2-12

0510

Fault Trace/Fault History
Clear Function
FLT Trace Init

Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.

0 ~ 1

0

Programming

o2-14

0512

kWh User Monitor (U1-
29) Initialization
kWh MonitorClear

Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to zero.

0 ~ 1

0

Programming

Copy Function

o3-01

0515

Copy Function Selection
Copy Function Sel

This parameter controls the copying of parameters to and from the digital
operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from the drive to the
digital operator.
2: OP -> INV WRITE - All parameters are copied from the digital operator
into the drive.
3: OP <--> INV VERIFY - Parameter settings in the drive are compared to
those in the digital operator.
Note: When using the copy function, the drive model number and software
number (U1-14) must match or an error will occur.

0 ~ 3

0

Programming

o3-02

0516

Read Allowed Selection
Read Allowable

Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are allowed.
1: Enabled - Copying allowed

0 ~ 1

0

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location