YASKAWA TM.iQp.10 Technical Manual Supplement

Preset Reference

d1-01



0280

Set-point Reference 1
Set-point 1

Digital preset setpoint reference 1. Used when b1-01 = 0 and when in
“hand” mode. Setting units are affected by P1-02.

1 ~ P1-03

Value

0.00 to

P1-02

Value

<0034>

0.00

Programming

d1-02



0281

Set-point Reference 2
Set-point 2

Digital preset setpoint reference 2. Selected via multi-function input
terminals. Setting units are affected by P1-02.
Parameter d1-02 is also the Zone 1 PI reference when b5-01 = 2.

<0034>

0.00

Programming

d1-03



0282

Set-point Reference 3
Set-point 3

Digital preset setpoint reference 3. Selected via multi-function input
terminals. Setting units are affected by P1-02.
Parameter d1-03 is also the Zone 2 PI reference when b5-01 = 2.

<0034>

0.00

Programming

d1-04



0283

Set-point Reference 4
Set-point 4

Digital preset setpoint reference 4. Selected via multi-function input
terminals. Setting units are affected by P1-02.
Parameter d1-04 is also the Zone 1 and 2 PI reference when b5-01 = 2.

<0034>

0.00

Programming

d1-17



0292

Jog Frequency Reference
Jog Reference

Jog reference used when a jog is selected via the LCD operator keypad.
This parameter is not available with the HOA operator. Setting units are
affected by o1-03.

0.00

Programming

 Denotes that parameter can be changed when the drive is running.

Reference Limits

d2-01

0289

Frequency Reference
Upper Limit
Ref Upper Limit

Determines maximum speed command, set as a percentage of parameter
E1-04. If speed command is above this value, actual drive speed will be
limited to this value. This parameter applies to all speed command sources.

0.0 ~

110.0 %

100.0 % Programming

d2-02

028A

Frequency Reference
Lower Limit
Ref Lower Limit

Determines minimum speed command, set as a percentage of parameter
E1-04. If speed command is below this value, actual drive speed will be set
to this value. This parameter applies to all speed command sources.

0.0 ~

110.0 %

0.0 %

Programming

d2-03

0293

Master Speed Reference
Lower Limit
Ref1 Lower Limit

Determines the minimum speed command, set as a percentage of
parameter E1-04. If speed command is below this value, actual drive speed
will be set to this value. This parameter only applies
to analog inputs A1 and A2.

0.0 ~

110.0 %

0.0 %

Programming

Jump Frequencies

d3-01

0294

Jump Frequency 1
Jump Freq 1

These parameters allow programming of up to three prohibited frequency
points for eliminating problems with resonant vibration of the motor/
machine. This feature does not actually eliminate the selected frequency
values, but will accelerate and decelerate the motor through the prohibited
bandwidth.

0.0 ~

200.0 Hz

0.0 Hz

Programming

d3-02

0295

Jump Frequency 2
Jump Freq 2

0.0 Hz

Programming

d3-03

0296

Jump Frequency 3
Jump Freq 3

0.0 Hz

Programming

d3-04

0297

Jump Frequency Width
Jump Bandwidth

This parameter determines the width of the deadband around each selected
prohibited frequency point. A setting of “1.0” will result in a deadband of
+/- 1.0 Hz.

0.0 ~

20.0 Hz

1.0 Hz

Programming

V/f Pattern

E1-01

0300

Input Voltage Setting
Input Voltage

Set to the nominal voltage of the incoming line.

155 ~

255.0

(240V)

310 to

510.0

(480V)

240 V

480 V

Programming

E1-03

0302

V/f Pattern Selection
V/f Selection

0: 50 Hz
1: 60 Hz Saturation
2: 50 Hz Saturation
3: 72 Hz
4: 50 Hz VT1
5: 50 Hz VT2
6: 60 Hz VT1
7: 60 Hz VT2
8: 50 Hz HST1
9: 50 Hz HST2
A: 60 Hz HST1
B: 60 Hz HST2
C: 90 Hz
D: 120 Hz
F: Custom V/F
FF: Custom w/o limit

0 ~ FF

F

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location