YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

13 Transducer Wiring using an External Power Supply

13

Transducer Wiring using an External Power Supply

‹

Simplex Pump System - Transducer Connection using Analog Input A2
(4 - 20 mA Mode)

A2 used for pressure transducer.

‹

Simplex Pump System - Transducer Connection using Analog Input A1
(0 - 10 Vdc Mode)

A1 used for flow meter, water level or suction pressure transducer.

Output

4-20mA

Transducer

V+

A2

AC

+V

EG

iQpump

+ -

External

24Vdc Power Supply

Set S1-2 to ON Position (4-20mA) for iQpump Drive (Factory Default)

O

F
F

1

2

S1-2

Output

4-20mA

Transducer

V+

A1

AC

+V

EG

250Ω

iQpump

Resistor 250 Ohm / 1% 1W
Refer to Page 242 of the
TM.iQp.06 User Manual for
gain and bias settings.

*

*

+ -

External

24Vdc Power Supply