YASKAWA TM.iQp.10 Technical Manual Supplement

69

L8-15

04BB

OL2 Characteristic
Selection at Low Speeds
OL2 Sel @ L-Spd

This parameter assists in protecting the output transistor junctions from
overheating when output current is high and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)

0 ~ 1

1

Programming

L8-18

04BE

Soft CLA Selection
Soft CLA Sel

Enables and disables current limit “A”.
0: Disabled
1: Enabled

0 ~ 1

1

Programming

L8-19 04BF

OH Frequency Reference
Reduction Level
Fref During OH

Sets the amount of frequency reference reduction when an Overheat Pre-
alarm (OH) is detected.

0.0 ~

100.0 %

20.0 %

Programming

Hunting Prevention

n1-01

0580

Hunting Prevention
Selection
Hunt Prev Select

0: Disabled (Hunting prevention function disabled.)
1: Enabled (Hunting prevention function enabled.)
If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration. There is a loss of responsiveness if
hunting prevention is enabled.

0 ~ 1

1

Programming

n1-02

0581

Hunting Prevention Gain
Setting
Hunt Prev Gain

Gain setting for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain
by 0.1 until vibration ceases. If the motor stalls while n1-01 = 1 decrease
the gain by 0.1 until the stalling ceases.

0.00 ~ 2.50

1.00

Programming

High-Slip Braking

n3-01

0588

High-Slip Braking
Deceleration Frequency
Width
HSB Decel Width

Sets how aggressively the drive decreases the output frequency as it stops
the motor. If overvoltage (OV) faults occur during HSB, this parameter
may need to be increased.
Note: Function Deactivated

1.0 ~

20.0 %

5 %

Programming

n3-02

0589

High-Slip Braking Current
Limit
HSB Current Ref

Sets the maximum current to be drawn during a HSB stop. Higher n3-02
settings will shorten motor stopping times but cause increased motor
current and therefore, increased motor heating.
Note: Function Deactivated

100.0 ~

200.0 %

150 %

Programming

n3-03

058A

High-Slip Braking Dwell
Time at Stop
HSB DwelTim@ Stp

Sets the amount of time the drive will dwell at E1-09 (Minimum
Frequency). If this time is set too low, the machine inertia can cause the
motor to rotate slightly after the HSB stop is complete and drive output is
shut off.
Note: Function Deactivated

0.00 ~

10.0 sec

1.0 sec

Programming

n3-04

058B

High-Slip Braking
Overload Time
HSB OL Time

Sets the time required for a HSB Overload Fault to occur when the drive
output frequency does not change for some reason during a HSB stop.
Normally this does not need to be adjusted.
Note: Function Deactivated

30.0 ~

1200.0 sec

40 sec

Programming

Monitor Select

o1-01



0500

User Monitor Selection
User Monitor Sel

Selects which monitor will be displayed upon power-up when
o1-02 = 4.

6 ~ 94

6

Programming

o1-02

0501

User Monitor Selection
After Power-Up
Power-On Monitor

Selects which monitor will be displayed upon power-up.
1: Auto: Set-point
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)

1 ~ 4

1

Programming

o1-05

0504

LCD Brightness
Adjustment
LCD Contrast

0 ~ 5

3

Programming

o1-06

0517

User Monitor Selection
Mode
Monitor Mode Sel

Selects the “U1” monitors displayed on the 4th and 5th lines of the digital
operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1 monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07 and o1-08.)

0 ~ 1

1**

Programming

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Set Value

Description

5

LCD display becomes dark

3

Standard setting

1

LCD display becomes light

Advertising