4 drive change summary, Overview, Drive change summary – Yaskawa iQpump Manual Supplement User Manual

Page 9: 4drive change summary

Advertising
background image

4 Drive Change Summary

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

9

4

Drive Change Summary

‹

Overview

The following is an overview of changes made the drive with software PRG: 0035 and PRG: 0036.

„

Drive Software Changes

Table 2 Parameter Enhancements for PRG: 0035

Table 3 Digital Input H1-…… Enhancements for PRG: 0035

Table 4 Digital Output H2-…… Enhancements for PRG: 0035

Table 5 Added H3-09 Analog Input Function for PRG: 0035

Parameter

Description

Page

A1-01 Language Selection Selection 6:Portuguese is removed.

40

A1-03 Initialization Mode Added selection 7770:General Purpose.

38

b1-01 Frequency

Reference Selection

Added selection 5:Geothermal Mode.

20

b1-03 Stop Method

Default changed from: Ramp to Stop (0) to Coast to Stop (1).

41

C6-02 Carrier Frequency

Default value changed to setting 1 (2.0 kHz) for all drive sizes.

41

P8-01 Water Lev./Suc.

Pres. Selection

Selection 1: Changed from Enabled to Water Level Control.

Added selection 2:Suction Pressure Control.

16

P8-09 Low Level Behavior Added selection 3:Auto-Restart (time set by P8-12).

17

P9-01 Lead Drive

Selection

Added selection 2:Stop History.

34

P9-05 Lag Drive Mode

Added selection 3:Follow Lead Speed.

29

P9-08 Add Pump Mode

Added selection 3:Flow Meter.

32

P9-12 Remove Pump
Mode

Added selection 3:Flow Meter.

33

P9-23 Max Pumps

Running

Range changed from 1 - 16 to 1 - 8.

Default changed from 16 to 8.

P9-25 Highest Node

Address

Range changed from 2 – 16 to 2 - 8.

42

Function

Description

Page

72 Remote Drive Disable

Digital Input function (normally open or normally closed) that can be used to prevent the
drive from running with a programmable delay time.

11

Function

Description

Page

4A Transducer Loss <1>

<1> Modified from previous version.

Closed: During a “Feedback Loss” alarm.

Closed: During a “FBL – Feedback Loss” fault”.

Closed: During an “A1-LOST Terminal A1 Lost” alarm. <1>New
Closed: During an “A1-LOST Terminal A1 Lost” fault. <1>New

36

57 Low Water Level <1>

This will energize if P8-01 = 1 and the level in the well drops below the Low Level

Detection Level (P8-07) for more than the Low Level Detection Delay Time
(P8-08), or if there is a LOWWL – Low Water Level Fault.

18

58 Low Suction Level

This will energize if P8-01 = 2 and the suction pressure drops below the Low Suction

Pressure Detection Level (P8-07) for more than the Low Suction Pressure Delay Time
(P8-08), or if there is a LOSUC – Low Suction Pressure Fault.

18

Function

Description

Page

20 Geothermal Mode

Temperature input for geothermal mode operation.

21