8 Geothermal Mode

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

25

„

Related Parameters for Geothermal Mode Operation

Parameter

Description

iQpump Controller

b1-01

Frequency Reference Source

5

b5-01

PI Mode

0

H3-09

Terminal A2 Function Selection

20

o1-06

User Monitor Selection Mode

1

o1-02 <1>

<1> After programming is completed, cycle power to the drive, as changes to the o1-02 monitor requires a drive power-up cycle to be effective.

User Monitor Selection After Power-Up

2

o1-08

Third Line User Monitor Selection

80

P1-01

Pump Mode

0

P4-31

Minimum Geothermal Temperature Input

0.0 °F

P4-32

Maximum Geothermal Temperature Input

120.0 °F

P4-33

Minimum Geothermal Speed

35.00 Hz

P4-34

Maximum Geothermal Speed

60.00 Hz

P4-35

Low Temperature to Run at Max. Geothermal speed

55.0 °F

P4-36

Low Temperature to Run at Min. Geothermal speed

65.0 °F

P4-37

High Temperature to Run at Min. Geothermal speed

75.0 °F

P4-38

High Temperature to Run at Max. Geothermal speed

85.0 °F

P4-39

Geothermal Temperature Loss Detection

1