8 Geothermal Mode

YASKAWA TM.iQp.10 iQpump Technical Manual Supplement

23

„

Geothermal Mode iQpump Controller Monitors

U1-80 Geothermal Temperature Input

Note: Only shown when b1-05 = 5 (Geothermal Mode)

„

Geothermal Temperature Loss Detection

P4-39 Geothermal Temperature Loss Detection

Selects iQpump Controller action when the temperature sensor signal from Terminal A2 is below 3 mA or above 21 mA.

Note: Only effective when H3-08 = 2 (4-20 mA) and H3-09 = 20 (Geothermal Temp).

Alarm: Temperature Sensor Lost (factory default)

Alarm: Geothermal Parameters Programming Error

Fault: Temperature Sensor Lost

Unit

Description

0.1 °F

Displays Geothermal temperature input after gain and bias are applied. This is the temperature used by the
Geothermal Function to determine what frequency to run the iQpump Controller.

Setting

Description

0

Disabled

1

Alarm (factory default)

2

Fault

Alarm Display

Description

Temp Lost

Geothermal Input

The geothermal temperature sensor is not present. Alarm occurs when:
1. b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 1 (Alarm), and the input has

either dropped below 3 mA or went above 21 mA.

Check: Ensure the device connected to Terminal A2 is installed and working properly.
2. b1-01 = 5, and H3-09

≠ 20 (Geothermal Temp), and P4-39 = 1 (Alarm).

Check: Terminal A2 must be assigned to Geothermal Temp (H3-09 = 20).
3. b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 2 (Fault), the drive is either
in HAND mode or has no run command, and the input is below 3 mA or above 21 mA.

Check: Ensure the device connected to Terminal A2 is installed and working properly.
4. b1-01 = 5, and H3-09

≠ 20 (Geothermal Temp), P4-39 = 2 (Fault), and the drive is either in HAND mode

or has no run command.

Check: Terminal A2 needs to be assigned to Geothermal Temp (H3-09=20).

Alarm Display

Description

Geo Params

Check P4-35~P4-38

The drive is running at the P4-31 level because of an incorrect setting.

The temperature parameter values must be set in the following order:
P4-35 < P4-36 < P4-37 < P4-38

Fault Display

Description

Temp Lost

Geothermal Input

The geothermal temperature sensor is not present. Fault occurs when:

1.b1-01 = 5, and H3-09

≠ 20 (Geothermal Temp), and P4-39 = 2 (Fault).

Check: Terminal A2 must be assigned to Geothermal Temp (H3-09 = 20).
2.b1-01 = 5, H3-09 = 20 (Geothermal Temp), H3-08 = 2 (4-20 mA), P4-39 = 2 (Fault), the drive is either in

HAND mode or has no run command, and the input is below 3 mA or above 21 mA.
Check: Ensure the device connected to Terminal A2 is installed and working properly.