YASKAWA TM.iQp.10 Technical Manual Supplement

P1-09



0608

High Feedback Level
High FB Level

The drive will display a “High Feedback Level (HFB)” alarm when the
feedback level rises above the programmed level. The alarm will turn off
when the feedback level falls below the programmed High Feedback Level
minus the Hysteresis Level (P1-13). This function is active during running
in the hand mode, auto mode, pre-charge and thrust-bearing mode.
If P1-01 = 3, parameter P9-18 uses this value to calculate the quick de-
stage feedback level.

<0034>

0.0 ~

6000.0

(system

units

P1-02)

155.0

(system

units

P1-02)

Programming

P1-10



0609

High Feedback Level Fault
Delay Time
Hgh Lvl Flt Time

The drive will initiate a “High Feedback Fault (HFB)” when the feedback
level rises above the programmed level for a time specified in P1-10. The
drive will coast to a stop when a fault occurs. This function is active during
running in all operation modes.
If P1-01 = 3, the function will stop all drives running on the network when
the system fault occurs.

<0034>

0 ~ 3600

sec

2 sec

Programming

P1-11



<0032>

0106

Maximum SetPoint
Difference
Max Set-point Diff

When the drive is running and the difference between the setpoint and the
feedback exceeds the level in P1-11 for the time specified in P1-12, the
drive will trip on a “Not Maintaining Set-point (NMS)”. The drive will
coast to a stop when a fault occurs. A value of 0 disables this function. This
function is only active during running while operating in auto mode.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.

<0034>

0.0 ~

6000.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P1-12



<0032>

0107

Not Maintaining Set-point
Time
Not Maint SP Tm

Delay time before a Not Maintaining Set-point fault occurs. Pump
protection criteria specified in P1-11 must be met for the drive to fault. The
drive will coast to a stop when a fault occurs. A value of 0 disables Not
Maintaining Set-point fault.

0 ~ 3600

sec

60 sec

Programming

P1-13



0108

Hysteresis Level
Hysteresis Level

Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.

0.0 ~ 100.0

(system

units

P1-02)

0.0 (system

units

P1-02)

Programming

P1-14



0109

Prime Loss Level
Prime Loss Level

Used to detect loss of prime in the pump. If output current drops below this
level for the time specified in P1-12 and the output frequency is at fmax, a
“Loss Of Prime” fault occurs. The drive will coast to a stop when a fault
occurs.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.

<0034>

0.0 ~

1000.0 A

0.0 A

Programming

P1-15



010A

Low/Hi Water Digital
Input Configuration
Water DI Config

<0034>

Sets the type of control operation
0: Low N.O. - Hi N.O. (Low Water Normally Open, High Water Normally
Open)

<0034>

1: Low N.C. - Hi N.O. (Low Water Normally Closed, High Water
Normally Open)

<0034>

2: Low N.O. - Hi N.C. (Low Water Normally Open, High Water Normally
Closed)

<0034>

3: Low N.C. - Hi N.C.(Low Water Normally Closed, High Water Normally
Closed)

<0034>

To use the low water function one of the digital inputs (H1-††=85) must
be programmed. The low water input can be used for a low water condition
or in combination with the pre-charge function to indicate the reservoir is
filled. The low water input fault is only active during running while
operating in auto mode.

0 ~ 3

0

Programming

P1-16



<0034>

87F

Loss of Prime Time
Prime Loss Time

Delay time before a Loss of Prime fault occurs. Pump protection criteria
specified P1-14 must be met for the drive to fault. On fault the drive will
coast to a stop.

1 ~ 600 sec

20 sec

Programming

 Denotes that parameter can be changed when the drive is running.

Pump Protection

P2-01

060A

Sleep Level Type
Sleep Lvl Type

Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm)

<0034>

4: Low Flow (Terminal A1 - Flow meter required)

<0034>

Note: Feedback depends on PID direction operation.
Displays a “Sleep” Alarm when active.

0 ~ 4

0

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location