YASKAWA TM.iQp.10 Technical Manual Supplement

zP9-50

<0034>

0878

Water Level Source
Water Lvl Source

Defines which signal to use for Water Level Control (P8-††) when P1-01
= 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01

3

0 ~ 3

0

Programming

„P9-50

<0035>

0878

Suction Pressure Source
Suction Pres Src

Defines which signal to use for Suction Pressure Control (P8-††) when
P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01

3

0 ~ 3

0

Programming

P9-99

<0036>

0875

Network Compatibility
Selection
Network Comp Sel

Determines the communication compatibility for the iQpump Memobus
Network
0: A-Version 30034
Use this mode if (ONE or MORE) iQpump Controllers on the network
have software version monitor U1-14=30034 and nameplate PRG: 0034.
1: B-Version 30035+
Use this mode if (NONE) of the iQpump Controllers on the network have
software version monitor U1-14=30034 and nameplate PRG: 0034.

0 ~ 1

1

Programming

Auto-Tuning

T1-02

0702

Motor Rated Power
Mtr Rated Power

Sets the motor rated power in kW.
Note: T1-02 should be left at the default value (last 3 digits of the drive
model number).

0.00 ~

650.0

kVA

Dependent

Auto-Tuning

T1-04

0704

Motor Rated Current
Rated Current

Sets the motor rated current. (Used only during an auto-tune.)

kVA

Dependent

kVA

Dependent

Auto-Tuning

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu