4.3 Basic Functions Settings

4-21

4

Ope

rat

ion

(2) Related Parameters

∗ The setting unit is a percentage of the rated torque.

Note: When using SEMI F47 function, set 1000 ms.

Parameter

Meaning

When Enabled Classification

Pn008

n.

0

[Factory setting]

Does not detect undervoltage.

After restart

Setup

n.

1

Detects warning and limits torque by host controller.

n.

2

Detects warning and limits torque by Pn424 and Pn425.
(Only in the SERVOPACK)

Pn424

Torque Limit at Main Circuit Voltage Drop

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 100

1%

*

50

Immediately

Setup

Pn425

Release Time for Torque Limit at Main Circuit

Voltage Drop

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 1000

1 ms

100

Immediately

Setup

Pn509

Instantaneous Power Cut Hold Time

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

20 to 50000

1 ms

20

Immediately

Setup

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque