9.1 Alarm Displays

9-19

9

Trou

blesh

ooting

A.d10:
Motor-load Position

Error Overflow

Motor rotation direction and

external encoder installation

direction are opposite.

Check the servomotor rotation

direction and the external encoder

installation direction.

Install the external encoder in the

opposite direction, or change the

setting of the external encoder

usage method (Pn002.3) to reverse

the direction.

Mounting of the load (e.g., stage)

and external encoder joint instal-

lation are incorrect.

Check the external encoder

mechanical connection.

Check the mechanical joints.

A.E02:
MECHATROLINK
Internal

Synchronization

Error 1

MECHATROLINK transmission
cycle fluctuated.

Remove the cause of transmission
cycle fluctuation at host controller.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.E40:
MECHATROLINK

Transmission Cycle

Setting Error

Setting of MECHATROLINK
transmission cycle is out of speci-
fications range.

Check the MECHATROLINK
transmission cycle setting.

Set the transmission cycle to the

proper value.

A.E50:
MECHATROLINK

Synchronization Error

WDT data of host controller was
not updated correctly.

Check the WDT data updating for
the host controller.

Update the WDT data at the host
controller correctly.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.E51:
MECHATROLINK

Synchronization

Failed

WDT data of host controller was
not updated correctly at the syn-
chronization communications
start, and synchronization com-
munications could not start.

Check the WDT data updating for
the host controller.

Update the WDT data at the host
controller correctly.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be

faulty. Replace the SERVOPACK.

A.E60:
MECHATROLINK

Communications error
(Reception error)

MECHATROLINK wiring is
incorrect.

Check the MECHATROLINK wir-
ings.

Correct the MECHATROLINK wir-
ing.
Connect the terminator correctly.

MECHATROLINK data recep-
tion error occurred due to noise
interference.

Take measures against noise. Check
the MECHATROLINK communi-
cations cable and FG wiring and
take measures such as adding ferrite
core on the MECHATROLINK
communications cable.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and

then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.E61:
MECHATROLINK

Transmission Cycle

Error
(Synchronization
interval error)

MECHATROLINK transmission
cycle fluctuated.

Check the MECHATROLINK
transmission cycle setting.

Remove the cause of transmission
cycle fluctuation at host controller.

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions