Motorola 68P02958C00-B User Manual

Page 270

Advertising
background image

APPENDIX A:

RS232 Adapter Cables

A-4

Optional Function

Description

15-pin Male

SPKR+

SPKR+

6

SPKR-

SPKR-

7

SWB+

Shrink Tube
(Ext. +12V DC)

4

RTU-to-RTU Connection Using MDLC Protocol through
RS232

To establish a link between two RTUs using MDLC protocol, the ports of both RTUs should
be defined as RS232 RTU-to-RTU (RS-Link). The ports of the two RTUs should be
connected by the FLN6457 and FLN6458 adapters, when the adapters are connected.

!

IMPORTANT

Do not connect between RTUs without the adapter cables. A direct connection will
cause a short circuit between the pins that have the same function.