Motorola 68P02958C00-B User Manual

Page 447

Advertising
background image

Error Messages

C-155

Error #844:

Userrom Plc module, Function %%
Cannot Find PLC address %% in download process or userrom not OK.

Can not perform PLC communication while application not loaded or during
application download.

Error #845:

Userrom Plc module, Function %%
Failed to find PLC address %% in PLC Table.

Define all PLC addresses in PLC Table.

Error #846:

Userrom Plc module, Function %%
When referring RTU PLC from rungs, you must define in IOLINK only the (z,x,y)
coordinates !
The length of each coordinate must be 1 byte !

I/O link definition error in PLC type column.

Error #847:

Userrom Plc module, Function %%
Destination PLC IOLINK data type error !

When referring RTU PLC from rungs, the data type of the column in I/O Link
must be defined as one of the following:

a) PLCBIT
b) PLCVAL
c) PLCFLT

Communication protocol format error. Consult product group.

Error #848:

Userrom Plc module, Function %%
The length of PLC column being scanned should not exceed 140 bytes !!!

Scan on PLC type column should not exceed 140 bytes.

Error #861:

The phone connection was established, but the RTU doesn't respond

Different Site ID of the addressed phone number.

Error #862:

ML_Dial: TX fail, probably the phone line was disconnected.

Can not transmit due to disconnected phone line.

Error #863:

No phone Book in flash memory.

Can not dial without phone book.

Error #875:

Status is 'wait for call' but the line is active.

The RTU software status and phone line status do not match; the line will be
disconnected.