Error Messages

C-141

Error #257:

Some Failure In Module %%.

Faulty FIFO communication in the specified module.

Error #258:

CLOCK fail flag in module %% is on.

The clock in the specified module is faulty.

Error #259:

I/O module: %% EE memory problem.

All the channels are calibrated, but the inner EE is problematic.

Error #260:

Analog input module: %% FIFO time-out.

The Analog Input module does not respond to the RTU CPU.

Error #261:

Mixed I/O module: %% analog input problem

There is a problem in the specified analog input of the Mixed I/O module.

Error #262:

I/O Module: %% analog output not calibrated.

The specified analog input of the Mixed I/O module is not calibrated.

Error #263:

I/O module: %% analog input calib. succeeded with borderline input.

Calibration succeeded but one of the measurements is out of range.

Error #264:

DI FAIL In Module %%.

The specified module (DI or Mixed I/O) is in FAIL.

Error #265:

AI FAIL In Module %%.

The AI module is in FAIL.

Error #266:

Relay Check Back (CB) FAIL In Module %%.

Incompatibility between desired and actual status in DSP outputs.

Error #267:

Module %%, Scale Factor or Threshold Changed From User Requested Value.

Incompatibility between desired and actual status in AO.

Error #268:

Module %%, DSP Not Ready.

The AC Analyzer module does not respond due to hardware or software
problems. Consult product group.

Error #269:

Module %%, DSP Reset.

The AC Analyzer module has reset itself. Hardware or software problems.
Consult product group.