B.5.
Setting Parameters Registers for Data Request
Parameter
#
Range
Default
Main Parameters
Starter Current
0
8..1400
58 (Amp.)
Motor Current
1
4..1750
58 (Amp.)
Line/Delta Configuration
2
0 (Line), 1 (Inside Delta)
0 (Line)
Undercurrent_FLT
3
0..90 (% of FLA)
0 (% of FLA)
Undercurrent_DLY
4
1..40
10 (Seconds)
O/C JAM Fault
5
200..850 (% of FLA)
850 (% of FLA)
O/C JAM Delay
6
0..50
5 (0.5 Sec.)
Overload_Class
7
75..150
115 (% of FLA)
Overload_Protect
8
1..10
4 (Seconds)
Undervoltage_FLT
9
120..600
300 (Volt)
UnderVoltage_DLY
10
1..10
5 (Seconds)
Overvoltage_FLT
11
150..750
480 (Volt)
Overvoltage_DLY
12
1..10
2 (Seconds)
Reserved
14..23
Start Settings
Soft Start Curve
24
0..10 (5..9 are reserved)
0 (Standard).
Kickstart Time
25
0..10 (Tenth Seconds)
0 (No Pulse)
Starting Voltage/Current
26
10..80
30 (% of full
voltage)
Current Limit
27
100..500
400 (% of FLA)
Ramp UP Time
28
1..90
10 (Seconds)
Max. Start Time
29
1..250
30 (Seconds)
Number of Starts
30
1..10 & (11 = OFF)
10
Duty Cycle Time
31
1..60
30 (Minutes)
Start_Lockout
32
1..60
15 (Minutes)
EOR Relay Delay
33
0..40
5 (Seconds)
Reserved
35..39
Stop Settings
Soft Stop Curve
40
0..10 (5..9 are reserved)
0 (Standard)
Ramp DOWN Time
41
1..30
10 (Seconds)
End Torque
42
0..10
0 (Minimum)
Reserved
43..47
Dual Settings
Starting VOLT-2
48
10..80 % of full voltage
30
Current Limit-2
49
100..500
400 % of FLA
Ramp UP-2
50
1..90
10 (Seconds)
Ramp DOWN-2
51
1..30
10 (Seconds)
Motor Current-2
52
5..1400
31 (Amp.)
Reserved
53..55
Slow SP & Saving Parameters
Energy Saving
56
1..10
0
Slow Sp eed TRQ.
57
1..10
8
Max_Slow_SP_Time
58
1..250
30 (Seconds)
Reserved
59..62