GE Industrial Solutions ASTAT BP User Manual
Page 114
ASTAT BP User Manual
114
GE Industrial Solutions
©2013 GE Company All Rights Reserved
C.13.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
C.14.
Dual Settings Object (74
HEX
–
1 Instance)
C.14.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.14.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
1
Starting VOLT-2
10-80
30
Get/Set
40049
2
Current Limit-2
100-
500
400
Get/Set
40050
3
Ramp UP-2
1-90
10
Get/Set
40051
4
Ramp DOWN-2
1-30
10
Get/Set
40052
5
Motor Current-2
5-1400
105
Get/Set
40053
C.14.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
C.15.
Slow SP & Saving Parameters Object (75
HEX
– 1 Instance)
C.15.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.15.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
1
Energy Saving
0-10
10
Get/Set
40057
2
Slow Speed TRQ.
1-10
8
Get/Set
40058
3
Max_Slow_SP_Time
1-250
30
Get/Set
40059
C.15.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single