GE Industrial Solutions ASTAT BP User Manual

Page 114

Advertising
background image

ASTAT BP User Manual

114

GE Industrial Solutions

©2013 GE Company All Rights Reserved

C.13.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

C.14.

Dual Settings Object (74

HEX

1 Instance)

C.14.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.14.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

1

Starting VOLT-2

10-80

30

Get/Set

40049

2

Current Limit-2

100-

500

400

Get/Set

40050

3

Ramp UP-2

1-90

10

Get/Set

40051

4

Ramp DOWN-2

1-30

10

Get/Set

40052

5

Motor Current-2

5-1400

105

Get/Set

40053

C.14.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

C.15.

Slow SP & Saving Parameters Object (75

HEX

– 1 Instance)

C.15.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.15.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

1

Energy Saving

0-10

10

Get/Set

40057

2

Slow Speed TRQ.

1-10

8

Get/Set

40058

3

Max_Slow_SP_Time

1-250

30

Get/Set

40059

C.15.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

Advertising