A.7.

Actual Data (3X References & 4X References)

Actual data includes measured values such as voltage and current. It includes both logic and statistical

information. All parameters are word (two bytes) parameters. The protocol supports only reading of these

parameters.

Parameter # is "1 based". The actual parameter address is 1 lower than parameter #. For example the address

of parameter #1 is 0 (30000).

The parameters have double mapping, at the following 3x & 4x references:

Note: Function 4 should be used to read 3x references and function 3 to read 4x references.


Parameter

# (3x) # (4x)

Comment

Logic Status

1

257

Logic status of ASTAT-BP. 1 indicates:

d15: ASTAT-BP Tripped.

d14: Motor Stopped.

d13: Motor in Soft Stop Process.

d12: Motor in Start Process.

d11: Motor is Running.

d10: Dual_Adjust On.

d9: Motor is running with Energy Save On.

d8: Motor is running at Slow Speed forward.

d7: Motor is running at Slow Speed reverse.

d6: Reserved

d5..d0: Reserved.

Motor Current

2

258

Current, % Im

Line Voltage

3

259

Line voltage, volts

Phase_Sequence

4

260

1: Correct Phase seq. 0 : Wrong Phase Seq.

Hardwired inputs

5

261

Discrete Hardwired control inputs:

d15..d8: Reserved.

d7: External fault.

d6: Reserved.

d5: Reserved.

d4: D.Adj / S.Spd / Rst (Programmable) Input.

d3: E.Save / Rvrs / Rst (Programmable) Input.

d2: Start Input.

d1: Soft Stop Input.

d0: Stop Input.

Dip_Switch

6

262

d15..d8: Reserved.

d7: Prevent Setting Lock - (right-most)

d6: Expanded Setting Ranges

d5: Language Selection.

d4: Language Selection.

d3: Reserved - Must be set to Off.

d2: Generator Starting - Set to Off.

d1: Reserved

d0: Min (OFF) / Max display pages- (left most)

Reserved

7..9

264..265

Frequency

10

266

Frequency [Hz]

Thermistor_Resistance

11

267

Thermistor resistance, tenth Kohm.

Reserved

12..16 268..272

Logic Status at Power Fail

17

273

Logic Status at Control Pwr Supply turn OFF.

Elapsed Run Time

18

274

Total Hours of Running Motor.

Number of Starts

19

275

Total Number Of Starts

Last_Start_Period

20

276

Duration of Last Start, Seconds.

Last_Start_Peak_I

21

277

Peak Current During Last Starting process

Reserved

22

278

Total_Trips

23

279

Total Number Of Trips