GE Industrial Solutions ASTAT BP User Manual
Page 26
ASTAT BP User Manual
26
GE Industrial Solutions
©2013 GE Company All Rights Reserved
4.7.2
Main Settings
12
– Page 1
Function &
Default
Range
Unit
Description
Language:
English
Spanish
German
Italian
English
Sets ASTAT-BP’s interface language
Starter Current
58 Amp.
8 – 1100
A
Sets ASTAT-BP’s Rated Current (Type Unit)
Check the name plate on the soft starter and make sure that
digits 4 to 7 of the model name are the same as the
Starter Current setting. For example the setting for
model QBx
0008Uxxx must be
8 Amp. Refer to section 5.1 on
page 47.
Motor Current
58 Amp.
8-1200
13
Based on % of
Starter
Current
A
Sets the motor’s Full load Ampere
Should be programmed as shown on the motor’s name
plate.
14
Note:
When setting
Motor Current to a higher level than
Starter Current, Overload Class parameter (see
below) is automatically sets to
NEMA Class 10.
RATED POWER
30KW
KW
Sets the motor’s rated power
Rated motor power is used for analog output reference.
Refer to section 4.7.8 on page 39 for
Analog Output
programming.
LINE/DELTA Conf.
Line
Line, Inside
Delta
Sets ASTAT-BP’s connection type.
15
Factory preset - features and functions not active when
DELTA Conf. is configured:
Kickstart.
Soft Start Curve selection (Curve 0!! only)
Slow Speed
Phase Sequence Disabled mode
Refer to section 8.7 on page 69 for further information.
Line Voltage
400 Volt
V
Sets rated line voltage
Undercurrent FLT
0% of Im
0%=OFF;
20-90
% of
Motor
Current
Sets Undercurrent protection.
Trips the ASTAT-BP when the motor current drops below the
level that was set for a time period longer than
Undercurrent Dly.
Undercurrent DLY
10 SEC.
1-40
sec.
Sets the time delay for Undercurrent FLT protection.
Note:
Operational when the motor is running (the RUN LED is lit).
12
Displays in MINIMIZED MODE and MAXIMIZED MODE.
13
The lower limit can be set as low as 50% of Starter Current. The upper limit is automatically set by the ASTAT-BP and is between 100 and 150% of
Starter Current.
The Motor Current can be set as high as indicated in columns “Current Rating” for Light Duty applications in the tables in section 2.1 page 8 and in
section 2.3 page 9.
14
When the ASTAT-BP is installed in the Inside Delta configuration set:
Motor Current = <rated motor current>/1.73.
15
When the ASTAT-BP is installed in DELTA Conf. set Motor Current = <rated motor current>/1.73.