GE Industrial Solutions ASTAT BP User Manual

Page 26

Advertising
background image

ASTAT BP User Manual

26

GE Industrial Solutions

©2013 GE Company All Rights Reserved

4.7.2

Main Settings

12

– Page 1

Function &

Default

Range

Unit

Description

Language:

English

Spanish

German

Italian

English

Sets ASTAT-BP’s interface language

Starter Current

58 Amp.

8 – 1100

A

Sets ASTAT-BP’s Rated Current (Type Unit)

Check the name plate on the soft starter and make sure that

digits 4 to 7 of the model name are the same as the

Starter Current setting. For example the setting for

model QBx

0008Uxxx must be

8 Amp. Refer to section 5.1 on

page 47.

Motor Current

58 Amp.

8-1200

13

Based on % of

Starter

Current

A

Sets the motor’s Full load Ampere

Should be programmed as shown on the motor’s name

plate.

14

Note:

When setting

Motor Current to a higher level than

Starter Current, Overload Class parameter (see

below) is automatically sets to

NEMA Class 10.

RATED POWER

30KW

KW

Sets the motor’s rated power

Rated motor power is used for analog output reference.

Refer to section 4.7.8 on page 39 for

Analog Output

programming.

LINE/DELTA Conf.

Line

Line, Inside

Delta

Sets ASTAT-BP’s connection type.

15

Factory preset - features and functions not active when

DELTA Conf. is configured:

Kickstart.

Soft Start Curve selection (Curve 0!! only)

Slow Speed

Phase Sequence Disabled mode

Refer to section 8.7 on page 69 for further information.

Line Voltage

400 Volt

V

Sets rated line voltage

Undercurrent FLT

0% of Im

0%=OFF;

20-90

% of

Motor

Current

Sets Undercurrent protection.

Trips the ASTAT-BP when the motor current drops below the

level that was set for a time period longer than

Undercurrent Dly.

Undercurrent DLY

10 SEC.

1-40

sec.

Sets the time delay for Undercurrent FLT protection.

Note:

Operational when the motor is running (the RUN LED is lit).

12

Displays in MINIMIZED MODE and MAXIMIZED MODE.

13

The lower limit can be set as low as 50% of Starter Current. The upper limit is automatically set by the ASTAT-BP and is between 100 and 150% of

Starter Current.

The Motor Current can be set as high as indicated in columns “Current Rating” for Light Duty applications in the tables in section 2.1 page 8 and in

section 2.3 page 9.

14

When the ASTAT-BP is installed in the Inside Delta configuration set:

Motor Current = <rated motor current>/1.73.

15

When the ASTAT-BP is installed in DELTA Conf. set Motor Current = <rated motor current>/1.73.