Under Voltage:

Trips when main voltage drops below 50-90% of

Line Voltage, time delay 1-

10 Sec. Optional Auto Reset.

Over Voltage:

Trips when main voltage increase above 110-125% of

Line Voltage, time

delay 1-10 sec.

Phase Loss, Under/over

Frequency:

Trips when one or two phases are missing, or frequency is < 40Hz or > 65Hz.

Optional auto reset.

Phase Sequence:

Trips when phase sequence is wrong

Long Slow Speed Time:

Trips if operating at slow speed TRQ for more than 1-30 sec (1-250 sec

3

)

Wrong Connection:

Prevents starting, trips if motor is not connected / incorrectly connected to the

ASTAT-BP (not active in

D.Set: Generator Parameters)

Shorted SCR:

Trips if one or more SCRs have been shorted

(not active in

D.Set: Generator Parameters)

Heat Sink Over

Temperature:

Trips when heat-sink temperature rises above 85°C

External Fault:

Trips when an external contact closes for 2 sec.

Motor Thermistor:

Trip level setting 1-10K

Control:

Displays:

LCD in 4 – Field selectable languages and 8 LEDs

Keypad:

6 keys for easy setting

Aux Contact –

Programmable:

1 NO, 8A, 250VAC, 2000VA

Fault Contact:

1 NO, 8A, 250VAC, 2000VA

Communication:

RS 485 with Modbus protocol for full control and supervision

Communication (optional):

Profibus DPV1 for full control and supervision

Communication (optional):

DeviceNet

tm

for full control and supervision

Temperatures Operating:

-10° to 60°C; For ambient temperature between 50°C and 60°C, derate the

current by 2.5% for each °C that is above 50°C

Storage:

-20° to 70°C

Standards:

Dielectric Test:

2500VAC

Degree of Protection:

IP 20 for QBx0008 - QBx0044 ; IP 00 for QBx0058 – QTx1100

Pollution Degree:

3

EMC

Emissions:

EN 61000-6-4 CISPR 11 Class A

Immunity:

EN 61000-6-2 ESD 8KV air, IEC 801-2;

Electric RF field 10 V/m, 20-1000Mhz, IEC 801-3

Fast transients 2KV, IEC 801-4

Safety:

UL508C

Rated Operational Current

AC:53a:3.5-30: 50-4

Normal Service Conditions:

Altitude:

Up to 1000m.

Humidity:

95% at 50°C or 98% at 45°C

Fan and Control Consumption Ratings:

QBx0008 to QBx0170: No fan

Total approximate consumption: 35VA

QBx0210 to QBx0477: Fans 50 VA

Total approximate consumption: 85VA

QBx0515 to QBx0840 : Fan 50 VA

Total approximate consumption: 100VA

QBx0960 to QBx1100 : Fans 110 VA

Total approximate consumption: 160VA