Attribute
ID
Name
Description
Access
Rule
Modbus
Address
02: Short Circuit Current
03: Overload
04: Under Current
05: Under Voltage
06: Over Voltage
07: Phase Loss
08: Phase Sequence
09: Shorted SCR.
10: Long Start Time
11: Slow Speed Time
12: Reserved
13: External Fault
14: Wrong Parameters
15: EMI/RFI Fault
16: Too Many Starts
17: Reserved.
18: Thermistor.
19: Frequency.
25
Motor Fault
Current
Current at trip time (Amp)
Get
40281
26-45
Actual_Data_Group
20 actual parameters selected
by Setting Parameters 90-109
Get
40365-
40384
C.10.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
C.11.
Main Parameter Object (71
HEX
–
1 Instance)
C.11.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.11.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
1
Starter Current
8-1400
(Amps)
58
Get/Set
40001
2
Motor Current
4-1750
(Amps)
58
Get/Set
40002
3
Line/Delta
Configuration
0 – Line
1 – Inside
Delta
0
Get/Set
40003
4
Undercurrent FLT
0-90 (% of
Im)
0
Get/Set
40004
5
Undercurrent DLY
1-40 (Sec)
10
Get/Set
40005
6
O/C JAM Fault
200-850
(% of Im)
400
Get/Set
40006
7
O/C JAM Delay
0-50
(0.5 Sec.)
5
Get/Set
40007
8
Overload Class
75-150
(% of Im)
115
Get/Set
40008
9
Overload Protect
1-10 (Sec.)
4
Get/Set
40009
10
Under voltage FLT
120-600
(Volt)
300
Get/Set
40010
11
Under voltage DLY
1-10 (Sec)
5
Get/Set
40011
12
Over voltage FLT
250-750
400
Get/Set
40012