GE Industrial Solutions ASTAT BP User Manual

Page 112

Advertising
background image

ASTAT BP User Manual

112

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Attribute

ID

Name

Description

Access

Rule

Modbus

Address

02: Short Circuit Current

03: Overload

04: Under Current

05: Under Voltage

06: Over Voltage

07: Phase Loss

08: Phase Sequence

09: Shorted SCR.

10: Long Start Time

11: Slow Speed Time

12: Reserved

13: External Fault

14: Wrong Parameters

15: EMI/RFI Fault

16: Too Many Starts

17: Reserved.

18: Thermistor.

19: Frequency.

25

Motor Fault

Current

Current at trip time (Amp)

Get

40281

26-45

Actual_Data_Group

20 actual parameters selected

by Setting Parameters 90-109

Get

40365-

40384

C.10.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

C.11.

Main Parameter Object (71

HEX

1 Instance)

C.11.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.11.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

1

Starter Current

8-1400

(Amps)

58

Get/Set

40001

2

Motor Current

4-1750

(Amps)

58

Get/Set

40002

3

Line/Delta

Configuration

0 – Line

1 – Inside

Delta

0

Get/Set

40003

4

Undercurrent FLT

0-90 (% of

Im)

0

Get/Set

40004

5

Undercurrent DLY

1-40 (Sec)

10

Get/Set

40005

6

O/C JAM Fault

200-850

(% of Im)

400

Get/Set

40006

7

O/C JAM Delay

0-50

(0.5 Sec.)

5

Get/Set

40007

8

Overload Class

75-150

(% of Im)

115

Get/Set

40008

9

Overload Protect

1-10 (Sec.)

4

Get/Set

40009

10

Under voltage FLT

120-600

(Volt)

300

Get/Set

40010

11

Under voltage DLY

1-10 (Sec)

5

Get/Set

40011

12

Over voltage FLT

250-750

400

Get/Set

40012