GE Industrial Solutions ASTAT BP User Manual

Page 40

Advertising
background image

ASTAT BP User Manual

40

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Function &

Default

Range

Unit

Description

Relay OFF Delay

0 SEC.

0 – 60

sec.

Sets ASTAT-BP’s auxiliary relay OFF Delay.

Analog Output

I, 0...200% OF Im

I, 0...200% OF Im

P, 0…200% OF Pn

POWER FACTOR

Sets Analog Output mode of operation

When analog card is installed, full scale of the

readings is related to:

l

200% of

motor current when set to I,

0…200% OF Im

l

200% of

RATED POWER when set to I, 0…200%

OF Pn

l

1 when set to

POWER FACTOR.

The dip switch settings on the analog card defines full

scale as either 20mA or 10V. Refer to section 5.6 on

page 49 for more details.

For

motor current and RATED POWER

programming refer to section 4.7.2 page 26.

Store Settings

I/O Settings

Same as

Store Settings Main Settings on

page 28.