B.2.

Configure the PROFIBUS in the ASTAT-BP

All the settings to establish PROFIBUS communication are located under the Communication menu. Follow the

steps below to define the PROFIBUS in the ASTAT-BP.

Press the SET PAGE button until the following message appears:

COMM. PARAMETERS

- **** -

Press SELECT FWD one time and the following message will appear:

COMM. PROTOCOL

PROFIBUS

In this menu, use the up/down arrows to define that the communication will be PROFIBUS.

Press SELECT FWD again and the following message will appear:

BAUD RATE

AUTO (PROFIBUS)

Press SELECT FWD again and the following message will appear:

PROFI.NETWORK ID

3

In this menu, use the up/down arrows to define the PROFIBUS Address of the ASTAT-BP.

Press SELECT FWD again and the following message will appear:

S.LINK PAR. SAVE

ENABLE

In this menu, use the up/down arrows to define whether to enable/disable writing of parameters via the

PROFIBUS.

Press SELECT FWD again and the following message will appear:

SER.LINK CONTROL

ENABLE

In this menu, use the up/down arrows to define whether to enable/disable control via the PROFIBUS.

Press SELECT FWD again and the following message will appear:

Store Settings

COMM. Parameters

Pressing the SET button stores the parameters in the ASTAT-BP memory.

B.3.

Watch Dog Definition

The Watch-Dog mechanism can be enabled or disabled only via the PROFIBUS controller.

When the Watch-Dog is enabled, the ASTAT-BP will stop the motor when there is a break in communication

between the controller and the device.