GE Industrial Solutions ASTAT BP User Manual

Page 62

Advertising
background image

ASTAT BP User Manual

62

GE Industrial Solutions

©2013 GE Company All Rights Reserved

To operate D.Set: Generator Parameters mode:

o Program PROG. Input C1 to GEN. START/STOP. Refer to section 4.7.8 page 39.

o Set the D.Set: Generator Parameters to the values necessary for the application (e.g.,

shorter

Ramp UP-2, lower Current Limit-2, etc.). Refer to section 4.7.5 page 35 for

parameters settings.

o Insert a contact between Control Supply and aux. input terminal C1 and signal to operate with

the

D.Set: Generator Parameters.

Note:

The

D.Set: Generator Parameters must not always be used when a diesel generator is supplying

the ASTAT-BP. Only use

D.Set: Generator Parameters when the normal starting process fails, i.e.

Shorted Scr or Wrong Connection faults occur, and only after you have tested and are sure that

the SCRs, motor and motor connections are not faulty.

WARNINGS

When operating in

D.Set: Generator Parameters, the motor must be loaded

to avoid vibration during starting and stopping.

It is recommended to disconnect the power factor capacitors when operating with a

diesel generator.

Advertising